Room, duct, immersion, outdoor and averaging temperature sensors and transmitters. Makers include ACI, Belimo, Greystone, Honeywell, Johnson Controls, KMC Controls, Senva, Siemens and Veris.
The sensing element must match the controller input. Thermistor curves (such as 10K Type 2 or Type 3), RTDs (100 or 1000 ohm platinum, Balco) and transmitter outputs (4-20 mA, 0-10 V) are not interchangeable. Then choose the mounting: room, duct probe, rigid or flexible averaging, immersion with a thermowell, strap-on or outdoor. Size an averaging element to the duct or coil cross-section, and a probe to reach the center of the duct or pipe.
Accuracy classes (Class B, Class A, 1/3 DIN, 1/10 DIN) and options such as NIST certificates and tamper-resistant covers narrow the choice.