01CT-5BP
Details
Details
01CT-5BP Pt1000 Cable Temperature Sensor, 8 in. Probe
Passive Pt1000 sensor for duct mounting with a flange, or pipe immersion with an immersion sleeve; stainless steel probe, plenum-rated cable.
Key Features
- Element: Pt1000
- Range: -40 to 300 deg F
- Enclosure: NEMA 4X / IP67
- Wiring: cable 6.5 ft (2 m), 2-wire
Product Specifications
| Manufacturer | Belimo |
|---|---|
| Model | 01CT5BP (01CT-5BP) |
| Output signal passive temperature | Pt1000 |
| Cable length | 6.5 ft (2 m) |
| Probe length | 8" (200 mm) |
| Probe diameter | 0.24" (6 mm) |
| Electrical connection | cable 6.5 ft (2 m), 2-wire |
| Cable specification | 1 pair shielded plenum cable, 22AWG tinned copper, green jacket, -40 to 300 deg F (-40 to 150 deg C), 300 V |
| Application | air water |
| Measured values | Temperature |
| Measuring range | -40 to 300 deg F (-40 to 150 deg C) |
| Measuring current | Pt100: <1 mA @ 32 deg F (0 deg C) Pt1000: <0.3 mA @ 32 deg F (0 deg C) Ni1000 (JCI): <5 mA @ 21 deg C (70 deg F) NTC10k2: <2 mA @ 77 deg F (25 deg C) NTC10k3: <2.7 mA @ 77 deg F (25 deg C) NTC20k: <0.5 mA @ 77 deg F (25 deg C) |
| Accuracy temperature passive | Passive sensors depending on used type Pt.. : +/-0.5 deg F @ 32 deg F (+/-0.3 deg C @ 0 deg C) Ni.. : +/-0.7 deg F @ 32 deg F (+/-0.4 deg C @ 0 deg C) NTC.. : +/-0.35 deg F @ 77 deg F (+/-0.2 deg C @ 25 deg C) |
| Time constant τ (63%) in water pipe | With thermowell A-22P-A.. and thermal contact fluid Typical 7 s with thermowell brass Typical 9 s with thermowell stainless steel |
| Time constant τ (63%) in the air duct | Typical 155 s @ 0 m/s Typical 35 s @ 3 m/s |
| Protection class IEC/EN | III, Protective Extra-Low Voltage (PELV) |
| Power source UL | Class 2 Supply |
| Degree of protection IEC/EN | IP67 |
| Degree of protection NEMA/UL | NEMA 4X |
| Certification IEC/EN | IEC/EN 60730-1 |
| Quality Standard | ISO 9001 |
| UL Approval | cULus acc. to UL60730-1A/-2-9, CAN/CSA E60730-1/-2-9 |
| Type of action | Type 1 |
| Rated impulse voltage supply | 0.8 kV |
| Method of mounting control | Surface mounted |
| Pollution degree | 3 |
| Ambient humidity | Max. 95% RH, non-condensing |
| Ambient temperature | -40 to 300 deg F (-40 to 150 deg C) |
| Fluid temperature | -40 to 300 deg F (-40 to 150 deg C) |