Differential and gauge pressure transmitters and switches, airflow measuring stations, pitot tubes and static pressure pickups. Makers include ACI, Belimo, Greystone, Honeywell, Johnson Controls, Senva, Siemens and Veris.
Choose a range just above the normal operating pressure, so the reading uses most of the sensor's span: about 0.1 to 0.25 in. WC for building or room pressure, 1 to 5 in. WC for duct static, and a few in. WC for filter differential. Wet media such as water or glycol need a sensor rated for wet differential pressure.
Then match the output (4-20 mA, 0-5 V, 0-10 V), the pressure connection (barb, NPT or flare) and any display or selectable ranges to the job.