141-0575 Differential Static Airflow Switch, 1 to 12 in. WC, SPST, Manual Reset
Normally closed contact opens on rising pressure and stays open until reset by hand.
For fan safety lockout on excess positive or negative pressure.
Use as a positive, negative or differential pressure switch by choice of port.
Factory set at minimum; setpoint field adjustable.
Air service only.
Static pressure sensor 269-062 and sensing kit 189-142 are sold separately.
Key Features
- Contact: NC, opens on rising pressure
- Rating: 15 A non-inductive at 120 to 277 VAC
Product Specifications
| Manufacturer | Siemens |
|---|---|
| Model | 1410575 (141-0575) |
| Product type | Differential static pressure airflow switch, manual reset |
| Series | SW 141 |
| Setpoint range | 1 to 12 in. WC (250 to 3000 Pa), field adjustable |
| Setpoint accuracy | +/-1.5 in. WC at 12 in. WC (+/-375 Pa at 3000 Pa) |
| Switch action | SPST, manual reset; NC, opens on rising pressure |
| Measured media | Air |
| Ambient temperature range | -40 to 180 deg F (-40 to 82 deg C) |
| Maximum overpressure | 0.5 psi (3.4 kPa) |
| Mounting position | Diaphragm in any vertical plane |
| Electrical rating | Non-inductive 15 A at 120 to 277 VAC; pilot duty 300 VA at 120 to 277 VAC |
| Conduit opening | One, 1/2 in. conduit size |
| Sample line connectors | Two, with nuts and ferrules, for 1/4 in. OD copper or poly tubing |
| Material | Aluminized steel |
| Factory setting | Minimum setpoint |
| Dimensions | 6.13 in. H x 3.88 in. W x 3.19 in. D |
| Approvals | UL MFHX File MH9888; CSA 1811M25 |
| Compatible accessories | 269-062 static pressure sensor (pitot); 189-142 static pressure sensing kit |