F4-CVM03050-0

SKU: F4CVM030500

This item is IN STOCK

Current Stock: 225

Details

Details

F4-CVM03050-0 VAV Box Controller with Integrated Actuator and DP Sensor, BACnet MS/TP or N2

Mounts directly on the VAV damper shaft and measures airflow with its built-in differential pressure sensor.

Supports a wireless FC bus and wireless sensors with added hardware.

Needs 24 VAC power and supports up to four NS Series network sensors on its SA bus.

Key Features

  • I/O: 3 UI, 2 CO, 3 BO
  • Actuator: 35 lb-in
  • DP sensor: -2 to 2 in. WC
  • Real-time clock

Product Specifications

ManufacturerJohnson Controls
ModelF4CVM030500 (F4-CVM03050-0)
ControllerFacility Explorer F4-CV Series VAV box controller
CommunicationBACnet MS/TP (default) or N2; Zigbee wireless with add-on hardware
Inputs and outputs3 universal inputs, 2 configurable outputs, 3 binary outputs (8 points)
Universal inputs0-10 VDC; 0-600k ohm resistive; RTD (1k nickel, 1k platinum, A99); NTC (10k Type L, 2.252k Type 2); dry contact
Configurable outputs0-10 VDC analog or 24 VAC triac binary; CO accuracy 0-10 VDC +/-200 mV
Binary outputs24 VAC triac (internal power)
Power source terminal+15 VDC, 35 mA total, for active input devices
Integrated actuator35 lb-in (4 Nm); minimum shaft length 1-3/4 in.
Position feedbackNone
Differential pressure sensor-2 to 2 in. WC; +/-0.5% full scale typical; +/-0.0006 in. WC at null
SA busUp to 10 wired SA bus devices including up to 4 NS Series network sensors
WRZ wireless sensorsUp to 9 (ZFR Pro router) or 5 (WRZ-7860)
Power24 VAC nominal (20-30 VAC), 50/60 Hz, Class 2; 10 VA typical, 14 VA maximum
AddressingRotary switches: MS/TP 4-127; N2 1-253
ProcessorRX64M 32-bit Renesas
Memory16 MB flash, 8 MB SDRAM
Real-time clock backupSuper capacitor, 72 hours minimum
TerminationsPluggable screw terminals; RJ-12 SA and FC bus ports
MountingDamper shaft with single set screw; duct with single screw
HousingABS and polycarbonate, UL94 5VB, IP20
Ambient operating32 to 122 deg F
Dimensions6.5 x 4.92 x 2.9 in.
ComplianceUL Listed (File E107041, UL 916); plenum suitable per NEC 300.22(C); FCC Class A; cUL; CE