TEC3630-14-000
Details
Details
TEC3630-14-000 TEC3000 Networked Thermostat Controller for RTUs and Heat Pumps with Economizer, BACnet MS/TP or N2, White
Controls up to two-stage rooftop units or up to three-stage heat pumps, each with an economizer.
Selects its network protocol in the field.
Needs 24 VAC power. Supply, outdoor, and remote temperature sensors are sold separately.
Key Features
- Inputs: 3 AI, 2 BI
- Dehumidification
- Occupancy sensor: no
Product Specifications
| Manufacturer | Johnson Controls |
|---|---|
| Model | TEC363014000 (TEC3630-14-000) |
| Application | Up to two-stage RTUs or up to three-stage heat pumps, with economizer |
| Network | Field-selectable BACnet MS/TP or N2 |
| Power | 19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC, Class 2 or SELV |
| Relay contacts | 19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV |
| Binary inputs | Dry contact, BI1 and BI2 |
| Analog inputs | Three (R SEN, SAT, OAT): nickel, platinum, A99B, 2.25k NTC, 10k NTC, 10k NTC Type 3, 0-10 VDC |
| Sensors | Local digital temperature and humidity |
| Occupancy sensor | No |
| Dehumidification | Yes |
| Heating setpoint range | 40 to 90 deg F |
| Cooling setpoint range | 54 to 100 deg F |
| Minimum deadband | 2 deg F |
| Accuracy | Temperature +/-0.9 deg F at 70 deg F; humidity +/-5% RH (20-80% RH) |
| Display | Backlit color |
| MS/TP network | Up to 100 devices per network engine; 4,000 ft maximum cable |
| USB port | 120 to 250 mA |
| Wire size | 18 AWG maximum, 22 AWG recommended |
| Ambient operating | 32 to 122 deg F, 95% RH maximum, noncondensing |
| Color | White, Johnson Controls logo |
| Compliance | BTL listed B-AAC; UL Listed (File E27734, UL 60730); FCC Part 15 Class B; cUL; CE; RCM |