NSB8BTN240-0
Details
Details
NSB8BTN240-0 NS8000 Network Room Temperature Sensor, Fixed Segment LCD Display
Connects to the Sensor Actuator (SA) bus of Johnson Controls Metasys, Facility Explorer, Verasys, and Smart Equipment controllers; it does not work as a standalone or analog sensor.
Adjusts setpoint and fan speed on a backlit LCD display, with a temporary occupancy override.
Draws its 15 VDC power from the SA bus.
Key Features
- Measures: temperature only
- Address: DIP switch 199-206
- Terminations: modular jack and screw terminals
Product Specifications
| Manufacturer | Johnson Controls |
|---|---|
| Model | NSB8BTN2400 (NSB8BTN240-0) |
| Sensing | Zone temperature (digital sensor) |
| Interface | Backlit LCD fixed segment display; setpoint and fan speed adjustment; temporary occupancy override; screen lockout |
| Occupancy sensor (PIR) | No |
| Logo | Johnson Controls logo |
| Color | White |
| Communication | BACnet MS/TP on the SA bus, auto-detect 9.6, 19.2, 38.4, or 76.8 kbps |
| Supply voltage | 9.8 to 16.5 VDC, 15 VDC nominal from SA bus |
| Current | 3 mA maximum base; 10 mA additional with backlight on |
| Address | DIP switch 199-206, factory set 199 |
| Terminations | Modular jack and screw terminal block |
| Wire size | Modular jack: 24 or 26 AWG, three twisted pair; screw terminals: 18 to 22 AWG |
| Temperature range | 32 to 104 deg F |
| Temperature accuracy | +/-1 deg F zone sensor; element +/-0.36 deg F at 70 deg F |
| Temperature resolution | +/-0.5 deg F |
| Default setpoint adjustment | 50 to 86 deg F in 0.5 deg steps |
| Ambient operating | 32 to 122 deg F, 10 to 90% RH, noncondensing |
| Mounting | Surface or vertical wallbox |
| Dimensions (H x W x D) | 5 x 3.4 x 1.1 in. |
| Compliance | UL Listed (File E107041, UL 60730-1); FCC Part 15 Class B; cUL; CE; RCM |