WLD2C05C002L00C003
Details
Details
2-Channel Water Leak Detector, 6.5 ft and 9.8 ft Sensing Cables
Does not detect pure water, ethylene glycol alone, gasoline, or oil.
Needs 12-27 VAC/DC power.
Key Features
- Relay outputs: 2 Form C (NO/NC) relay alarms, one per channel
- Channel 1 leader cable: 16.4 ft (5 m)
Product Specifications
| Manufacturer | Greystone |
|---|---|
| Model | WLD2C05C002L00C003 |
| Sensing method | 2 independent channels |
| Channel 1 | Conductivity cable, 6.5 ft (2 m) |
| Channel 1 leader cable | 16.4 ft (5 m) |
| Channel 2 | Conductivity cable, 9.8 ft (3 m) |
| Channel 2 leader cable | None |
| Relay outputs | 2 Form C (NO/NC) relay alarms, one per channel |
| Alarm conditions | Water detected, power lost to the unit, or internal failure |
| Visual indication | Tri-color LED: green, yellow, red |
| Power supply | 12-27 VAC/DC, 50/60 Hz, SELV, Class 2 |
| Consumption | 125 mA max @ 24 VAC |
| Relay rating | 2A @ 30 VAC/DC, resistive, 6000 cycles, 140 deg F (60 deg C), SELV, Class 2; 0.5A @ 120 VAC |
| Operating temperature | 32 to 140 deg F (0 to 60 deg C) |
| Dimensions | 5.2 x 3.4 x 2.4 to 3.4 in. L x W x H (133.2 x 86.7 x 60.3 to 85.7 mm) |
| Enclosure | Type 4X and IP65, ABS with hinged and gasketed cover |
| Mounting | Floor of the monitored area or a nearby wall; height-adjustable legs with 5 preset heights |
| Leader cable type | FT-6 plenum rated |
| Detects | City water, sea water, copper sulfate solution, weak acid, weak base, household ammonia, water and glycol mixture, wet soil, coffee |
| Does not detect | Pure water, gasoline, oil, brake fluid, alcohol, ethylene glycol, paraffin, dry soil, whiskey |
| Protection class | III |
| Purpose of control | Operating control, water detector |
| Type of action | Type 1.C |
| Impulse voltage | 330V |
| Pollution degree | 3 |
| Certification | UL 60730 and CSA E60730 |
| Air handling spaces | UL 2043 / CSA / ULC S142 compliant: suitable for use in air handling spaces per Section 300.22(C) of the National Electrical Code |
| UL model numbers (series) | WH2O22CC |
| EU conformity | CE |
| Country of origin | Canada |
| Sensing cable plenum rating | CL2P (UL) |
| Sensing cable shear strength | Over 180 lb (81.65 kg) |
| Sensing cable cut-through resistance | Over 40 lb (18.14 kg) with a 0.005 in. (0.127 mm) blade |
| Sensing cable abrasion resistance | 60 cycles per UL 719 |
| Sensing cable operating environment | 32 to 167 deg F (0 to 75 deg C); 5 to 95% RH, non-condensing; 15,000 ft (4,572 m) max altitude |
| Sensing cable storage temperature | -22 to 185 deg F (-30 to 85 deg C) |
| Sensing cable certifications | CE, UL CL2P, RoHS compliant, plenum rated |