VG7842ET+72CHGC

SKU: VG7842ET72CHGC
$1,276.84

Call for Availability - (510) 636-7900

Details

Details

VG7842ET+72CHGC 1/2 in. NPT 3-Way Mixing Globe Valve, 1.8 Cv, with VA7820-HGC-2 Spring Return (Stem Up) Proportional Actuator, Two Auxiliary Switches, 24 VAC

Springs back on power loss to close the inline (NC) port and open the lower (NO) port.

Takes on/off, floating, 0-10V, 2-10V, 0-20mA or 4-20mA control, chosen by switch settings.

Handles hot or chilled water up to 50% glycol to 284 deg F, or steam to 38 psi.

Key Features

  • Cv: 1.8
  • Trim: brass, linear flow
  • Force: 180 lb
  • Stroke time: 48 s
  • Auxiliary switches: two SPDT

Product Specifications

ManufacturerJohnson Controls
ModelVG7842ET72CHGC (VG7842ET+72CHGC)
ValveVG7842ET cast bronze globe valve, 3-way mixing
Size and connection1/2 in. (DN15) NPT
Cv1.8 (Kv 1.6)
Flow characteristicLinear
TrimBrass plug, brass seat against molded elastomeric disk; stainless steel stem; EPR packing
Valve stroke5/16 in. (8 mm)
Fluid temperature35 to 284 deg F (2 to 140 deg C) water; 38 psig saturated steam
Maximum allowable pressureWater 400 psig to 150 deg F, 365 psig at 248 deg F; steam 35 psig at 284 deg F
Body ratingANSI B16.15 Class 250
Maximum recommended pressure dropWater 35 psig; steam 15 psig
RangeabilityGreater than 100:1
Leakage0.01% of maximum flow per ANSI/FCI 70-2, Class 4
Valve ambient35 to 150 deg F
ActuatorVA7820-HGC-2 spring return (valve stem up), direct mount, brushless motor
Power24 VAC (19 to 30 VAC) at 50/60 Hz, Class 2
Minimum transformer size11 VA
Control signal0 to 10 VDC, 2 to 10 VDC, 0 to 20 mA, or 4 to 20 mA, switch selectable; custom start 0 to 6 VDC, end 3 to 10 VDC; on/off or floating 24 VAC by switch setting; direct or reverse acting; factory set 0 to 10 VDC direct acting
Input impedanceVoltage 100k ohm; current 120 ohm
Feedback signal0 (2) to 10 VDC, matches input range
Auxiliary switchesTwo SPDT, 230 VAC, 3.0 A resistive, 1/4 hp
Stroke time48 seconds (slow, factory setting) or 24 seconds (fast) for 5/16 in. stroke
Spring return directionValve stem up (actuator stem retracted)
Actuator force180 lb (800 N) minimum
Manual override5 mm Allen wrench
Electrical connections48 in. (1.2 m) UL 758 Type AWM halogen-free cable, 18 AWG
Mounting positionUpright or less than 90 deg from vertical for fluid to 212 deg F; stem horizontal with insulated pipe above 212 deg F
Actuator enclosureNEMA 2 (IP54)
Cycles100,000 full stroke cycles
Actuator ambient operating23 to 131 deg F (-5 to 55 deg C), 10 to 90% RH noncondensing
Actuator dimensions9.6 x 4.56 x 8.35 in. (244 x 116 x 212 mm)
Actuator listingsUL 60730 Listed, CCN XAPX, File E194024; CE