V48AL-2C

SKU: V48AL2C
$833.23

Call for Availability - (510) 636-7900

Details

Details

V48AL-2C 1 in. Union 3-Way Pressure-Actuated Water-Regulating Valve, 145-190 psi Opening Point, Factory Set 165 psi

Opens on a rise in refrigerant pressure at the bellows.

Port 1 is the inlet from the cooling tower, port 2 feeds the condenser, and port 3 is the bypass.

Water supply is limited to 150 psig and 170 deg F.

Key Features

  • Range: 145 to 190 psi, adjustable
  • Maximum pressure: 320 psi refrigerant

Product Specifications

ManufacturerJohnson Controls
ModelV48AL2C (V48AL-2C)
ValveV48 Series 3-way pressure-actuated water-regulating valve with union fittings, direct acting
Size and connection1 in. union
Range145 to 190 psi (1,000 to 1,310 kPa) opening point adjustment range
Factory setting165 psi (1,138 kPa) opening point, port 1 to port 2
Maximum pressure320 psi (2,206 kPa) refrigerant at bellows
Max. inlet pressure, water150 psig (1,034 kPa)
Max. fluid temperature170 deg F (77 deg C) water supply
Pressure connectionCopper capillary with 1/4 in. SAE female flare connector (includes valve stem depressor)
BodyCast iron with rust-resisting finish
MaterialsExtension sleeve, disc, stud, and disc holder brass; valve seat aluminum bronze; valve disc Buna-N; diaphragm nylon-reinforced Buna-N
Sensing elementBrass and phosphor bronze bellows in brass cup
Mounting positionVertical with range adjustment screw on top
Repair kitSeat repair kit STT17A-616R; sensing element replacement kit SEP107A-602R
Shipping weight12.4 lb (5.6 kg)