V146GL1-001C
Details
Details
V146GL1-001C 1 in. 2-Way Pressure-Actuated Water-Regulating Valve, Union Sweat, 200-400 psi Opening Point
Regulates condenser water flow to hold refrigerant head pressure.
For standard, non-corrosive high-pressure refrigerants.
Not for potable water systems.
Key Features
- Setpoint range: opening point 200 to 400 psi, factory set 275 psi
- Connection: Style 5
Product Specifications
| Manufacturer | Johnson Controls |
|---|---|
| Model | V146GL1001C (V146GL1-001C) |
| Valve series | V146 2-way pressure-actuated water-regulating valve |
| Valve size | 1 in. |
| End connections | Union (sweat) |
| Pressure connection | Style 5: 1/4 in. SAE male flare connector (7/16-20 UNF) |
| Setpoint range | Opening point 200 to 400 psi |
| Factory setting | Opening point 275 psi |
| Maximum pressure | 630 psi maximum working pressure |
| Media | Water pressure 350 psi maximum; glycol/water or liquids with low freezing points compatible with valve materials, -4 to 170 deg F |
| Maximum operating differential pressure | 60 psi recommended across the valve |
| Dimensions | A 4-3/4, B 2-13/16, C 10-1/2, D 5-15/16, E 4-9/16 in. |
| Replacement parts | Sensing element SEP38A-603R |
| Shipping weight | 9.3 lb (4.0 kg) |