V146EK-1C
Details
Details
V146EK-1C 3/4 in. 2-Way Pressure-Actuated Water-Regulating Valve, Union Sweat, 70-260 psi Opening Point
Regulates condenser water flow to hold refrigerant head pressure.
For standard, non-corrosive refrigerants.
Not for potable water systems.
Key Features
- Setpoint range: opening point 70 to 260 psi, factory set 165 psi
- Connection: Style 46
Product Specifications
| Manufacturer | Johnson Controls |
|---|---|
| Model | V146EK1C (V146EK-1C) |
| Valve series | V146 2-way pressure-actuated water-regulating valve |
| Valve size | 3/4 in. |
| End connections | Union (sweat) |
| Pressure connection | Style 46: copper capillary with 1/4 in. SAE female flare connector, valve stem depressor included |
| Setpoint range | Opening point 70 to 260 psi |
| Factory setting | Opening point 165 psi |
| Maximum pressure | 370 psi maximum refrigerant pressure |
| Media | Water pressure 350 psi maximum; glycol/water or liquids with low freezing points compatible with valve materials, -4 to 170 deg F |
| Maximum operating differential pressure | 60 psi recommended across the valve |
| Dimensions | A 3-3/8, B 2-3/16, C 7-3/16, D 4-3/16, E 3 in. |
| Replacement parts | Seat STT16A-622R; diaphragm DPM16A-622R; sensing element SEP38A-600R |
| Shipping weight | 4.3 lb (2.0 kg) |