TXSLA12ZW020E002
Details
Details
Slab Temp Transmitter, 65.6 ft Zip Wire, 0-10V, 32 to 122 deg F, Class B RTD
Installs in a conduit or copper tube cast into the slab.
Needs 15-35 VDC or 15-28 VAC power.
Key Features
- Wire length: 65.6 ft
- Sensor accuracy: +/-0.54 deg F
- Probe sensing range: -40 to 212 deg F
- Enclosure: ABS, UL94-V0, IP65 (NEMA 4X)
Product Specifications
| Manufacturer | Greystone |
|---|---|
| Model | TXSLA12ZW020E002 |
| Sensor | 1000 ohm platinum RTD, IEC 751, 385 alpha, thin film |
| Sensor accuracy | +/-0.54 deg F (+/-0.3 deg C) @ 32 deg F (0 deg C) |
| Probe sensing range | -40 to 212 deg F (-40 to 100 deg C) |
| Wire | PVC zip wire, 22 AWG |
| Wire length | 65.6 ft (20 m) |
| Probe material | Thermal conductive coating |
| Installation | Inside conduit or copper tubing embedded in the slab |
| Output | 0-10 VDC (factory configured) |
| Scaled range | 32 to 122 deg F (0 to 50 deg C) |
| Transmitter accuracy | +/-0.1% of span, including linearity |
| Calibration | Factory calibrated; field adjustment voids the warranty |
| Output drive @ 24 VDC | 10k ohm minimum load (voltage output) |
| Maximum output | Limited to <10.5 VDC |
| Input voltage effect | Negligible over specified operating range |
| Protection circuitry | Reverse voltage protected and output limited |
| Ambient operating range | -40 to 140 deg F (-40 to 60 deg C), 5 to 95% RH non-condensing |
| Enclosure | ABS, UL94-V0, IP65 (NEMA 4X) |
| Enclosure dimensions | 3.25 x 2.75 x 2.05 in. (82.5 x 69.8 x 52.0 mm) |
| Termination | Screw terminal block (14 to 22 AWG) |
| Protection class | III |
| Power supply | 15-35 VDC or 15-28 VAC SELV (Class 2) |
| Consumption | 5 mA |
| EU conformity | CE |
| Certification | UL 60730 and CSA E60730 |
| Plenum rating | UL 2043 / CSA / ULC S142: suitable for use in air handling spaces per NEC Section 300.22(C) |
| Purpose of control | Operating control |
| Type of action | Type 1 |
| Impulse voltage | 330 V |
| Pollution degree | 2 |
| Country of origin | Canada |