TXDRE12GA002

SKU: TXDRE12GA002
$282.44

Call for Availability - (510) 636-7900

Details

Details

Rigid Averaging Duct Temp Transmitter, 24 in. Probe, 4-20mA, 32 to 122 deg F, Class B RTD

Runs on 15-35 VDC loop power or 22-28 VAC.

Key Features

  • Sensor accuracy: +/-0.54 deg F
  • Probe sensing range: -40 to 140 deg F
  • Enclosure: ABS, UL94-V0, IP65 (NEMA 4X), with thread adapter (1/2 in. NPT to M16) and cable gland fitting

Product Specifications

ManufacturerGreystone
ModelTXDRE12GA002
Sensor1000 ohm platinum RTD, IEC 751, 385 alpha, thin film
Sensor accuracy+/-0.54 deg F (+/-0.3 deg C) @ 32 deg F (0 deg C)
Probe sensing range-40 to 140 deg F (-40 to 60 deg C)
WirePVC/Kynar, 28 AWG
Probe material304 series stainless steel
Probe diameter0.236 in. (6 mm)
Probe length24 in. (600 mm)
Output4-20mA current loop (factory configured)
Scaled range32 to 122 deg F (0 to 50 deg C)
Transmitter accuracy+/-0.1% of span, including linearity
CalibrationFactory calibrated; field adjustment voids the warranty
Input voltage effectNegligible over specified operating range
Protection circuitryReverse voltage protected and output limited
Ambient operating range-40 to 140 deg F (-40 to 60 deg C), 5 to 95% RH non-condensing
EnclosureABS, UL94-V0, IP65 (NEMA 4X), with thread adapter (1/2 in. NPT to M16) and cable gland fitting
Enclosure dimensions3.25 x 2.75 x 2.05 in. (82.5 x 69.8 x 52.0 mm)
TerminationScrew terminal block (14 to 22 AWG)
Protection classIII
Power supply15-35 VDC (loop-powered) or 22-28 VAC Limited Energy, <15 W
Consumption20 mA
EU conformityCE
CertificationUL 60730 and CSA E60730
Plenum ratingUL 2043 / CSA / ULC S142: suitable for use in air handling spaces per NEC Section 300.22(C)
Purpose of controlOperating control
Type of actionType 1
Impulse voltage330 V
Pollution degree2
Country of originCanada

Product Resources