TSENSE

SKU: TSENSE
$551.19

Call for Availability - (510) 636-7900

Details

Details

Room CO2, RH, and Temp Transmitter, 0-2000 ppm, 0-10V, Relay, BACnet MS/TP or Modbus RTU

Needs 12 VDC or 24 VAC/DC power. Needs ABC self-calibration turned off where the space is occupied 24 hours a day. Needs the TTL-232R-3V3-AJ programming cable, sold separately, for BACnet or Modbus settings.

Key Features

  • Coverage area: 7500 sq ft maximum

Product Specifications

ManufacturerACI
ModelTSENSE
ACI item number135459
MeasurementsCarbon dioxide (CO2), temp, and RH
CO2 sensing methodSingle beam non-dispersive infrared (NDIR)
CO2 sensing range0 to 2000 ppm, optional 0 to 3000 ppm
CO2 accuracy+/-50 ppm at 1000 ppm, 63 to 82 deg F (17 to 28 deg C); typical full range +/-30 ppm +/-3% of reading
Extended range accuracyTypically under +/-30 ppm +/-20% of measured value
CO2 repeatability+/-20 ppm +/-1% of measured value
CO2 annual zero drift+/-0.3% of measurement range
CO2 response time (T1/e)Under 3 minutes diffusion time
CO2 calibrationSenseair ABC (automatic baseline correction); building CO2 must drop to 400 ppm some time each week, and ABC must be turned off where the space is occupied 24 hours a day
CO2 sensor lifeOver 15 years typical
Temp range32 to 122 deg F (0 to 50 deg C)
Temp accuracy+/-0.9 deg F at 63 to 82 deg F (+/-0.5 deg C at 17 to 28 deg C); +/-1.8 deg F at 32 to 122 deg F
Temp repeatability+/-0.45 deg F at 63 to 82 deg F (+/-0.25 deg C at 17 to 28 deg C)
Temp response timeUnder 6 minutes (air velocity 0.15 m/s)
RH sensorCapacitive, 0 to 100% RH
RH accuracy+/-5% at 20 to 80% RH
RH hysteresis / annual drift+/-1% at 20 to 80% RH / under +/-0.5% RH
RH response timeUnder 6 minutes (air velocity 0.15 m/s)
Analog outputsOut 1 (CO2): 0-10V, 0 to 2000 ppm; Out 2 (temp): 0-10V, 32 to 122 deg F (0 to 50 deg C); Out 3 (RH): 0-10V, 0 to 100% RH
Analog output signalVoltage 0-10V, ROUT under 100 ohm, load over 5k ohm; 10-bit resolution
RelayForm C, SPDT, 1A at 50 VAC / 24 VDC; trip point 1000 ppm CO2 (factory set), deadband 100 ppm; input source CO2 (default), temp, or RH
Relay durabilityMechanical 100,000,000 operations minimum; electrical 100,000 operations minimum
Communication protocolModbus RTU or BACnet MS/TP; baud rates 9600, 19200, 38400, 57600, 76800, 115200; BACnet MAC address 0 to 127 (default 104)
ConfigurationTTL-232R-3V3-AJ programming cable (sold separately) and UIP5 software; the cable is required for BACnet or Modbus settings
DisplayNone
Supply voltage12 VDC or 24 VAC/VDC +/-20% (half-wave rectified), 50/60 Hz
Power consumptionUnder 0.35 W average, under 2 W maximum
Electrical connections0.00232 sq in. (1.5 mm2) screw terminals
Operating environmentResidential and commercial spaces
Operating temp / RH32 to 122 deg F (0 to 50 deg C), 0 to 95% RH non-condensing
Warm-up time1 minute; 15 minutes to full specifications
Coverage area7500 sq ft maximum
Mounting height4 to 6 ft off the floor
EnclosureBayblend FR3000 (PC/ABS blend), UL94V-0
Dimensions (H x W x D)4.92 x 3.35 x 0.87 in. (125 x 85 x 22 mm)
Weight0.361 lb (0.166 kg)
Agency approvalsEMC directive 2004/108/EC, RoHS directive 2011/65/EU; complies with ASHRAE 189.1; compliant with CA Bill 841
Warranty5-year limited