SFD212EG4YA07D07
Details
Details
3 HP (2.2 kW) Enclosed VFD with Full-Voltage Bypass, 460 VAC 3-Phase, UL Type 1, Drive Input Disconnect and Full Text Keypad
NEMA 1, 460V 3-phase VFD with bypass, drive input disconnect and text keypad. The text keypad uses the RJ-45 port, so Modbus isn't available there.
Key Features
- Output current: 4.8 A
- Input current: 4.9 A
- Bypass overload relay range: 4 to 6 A
- Control power transformer: 120 VAC, 100 VA, fused
- Short-circuit rating: 100,000 A symmetrical
Product Specifications
| Manufacturer | Schneider Electric |
|---|---|
| Model | SFD212EG4YA07D07 |
| Series | S-Flex 212 enclosed drive (Square D) |
| Power converter | Altivar 212 ATV212HU22N4 |
| Horsepower rating | 3 HP, variable torque |
| Kilowatt rating | 2.2 kW |
| Input voltage | 460 VAC +/-10%, three-phase |
| Input frequency | 50/60 Hz +/-5% |
| Input current | 4.9 A |
| Output current | 4.8 A |
| Max transient output current | 5.6 A |
| Output voltage | Three-phase, maximum equal to input voltage |
| Dissipated power at rated load | 224.7 W |
| Switching frequency | Selectable 6 to 16 kHz; factory setting 12 kHz |
| Rating conditions | 12 kHz switching frequency, 104 deg F (40 deg C) ambient |
| Short-circuit rating | 100,000 A symmetrical |
| Displacement power factor | Approximately 0.96 |
| Frequency range | 0.5 to 200 Hz (factory setting 60 Hz maximum) |
| Current limit | 110% of drive full load current for 60 s |
| Speed reference | VIA: 4-20mA (factory setting), 0-20mA or 0-10 VDC; VIB: 0-10 VDC |
| Analog output | Configurable (FM) |
| Frequency resolution | 0.0048 Hz (11 bits) on analog reference |
| Speed accuracy | +/-10% of nominal slip without speed feedback, 20 to 100% of motor rated torque |
| Efficiency | Typically greater than 95% |
| Acceleration and deceleration ramps | 0.1 to 3200 s in 0.1 s steps; factory setting 60 s |
| Factory speed range | 15 to 60 Hz (low and high speed settings) |
| Bypass | Full-voltage bypass (power circuit Y): drive output and bypass contactors with electrical interlock |
| Main disconnect | Square D circuit breaker HLL36015LV |
| Drive output and bypass contactors | LC1D25G7 |
| Overload relay | Class 10, LRD10 |
| Bypass overload relay range | 4 to 6 A |
| Motor protection | Class 10 overload relay in bypass plus drive internal electronic thermal protection |
| Power fuses | Class CC, 7 A (25430-20700) |
| Drive input disconnect | Disconnect switch between the main disconnect and the drive (A07) |
| Control power transformer | 120 VAC, 100 VA, fused |
| Selector switches | AFC-Off-Bypass (Series D); Hand-Off-Auto and AFC-Bypass (Series E) |
| Pilot lights | Power On (red) and Bypass Run (green), 120 VAC LED |
| Smoke purge | 120 VAC signal at TB1-17/18 transfers the motor to line power |
| Damper control | Open-damper relay contact (TB1-19/20) and damper end switch input |
| Auxiliary contacts | System run (NO, drive or bypass); AFC trip; Form C AFC fault |
| Freeze/firestat interlock | Input for user-supplied NC interlock (factory jumper installed) |
| Local/remote | Configurable on the enclosed drive |
| Communication | RJ-45 Modbus port used by the D07 keypad; factory set for terminal control |
| Keypad | Full text graphic keypad, door mounted, 8 languages (D07) |
| Enclosure | UL Type 1, general indoor (ventilated), plenum rated |
| Frame size | A |
| Mounting | Wall mount |
| Control terminals | 24 to 16 AWG, one wire per terminal, 5.3 to 7.1 lb-in |
| Operating temperature | 14 to 104 deg F (-10 to 40 deg C) |
| Storage temperature | -13 to 158 deg F (-25 to 70 deg C) |
| Humidity | 95% with no condensation or dripping water (IEC 60068-2-3) |
| Altitude | 3,300 ft (1000 m) without derating; derate current 1% per additional 330 ft (100 m) up to 10,000 ft (3000 m) |
| Pollution degree | 2 (NEMA ICS-1, IEC 60664-1) |
| Vibration (power converter) | 1.5 mm peak to peak from 3 to 13 Hz; 1 g from 13 to 150 Hz (IEC 60068-2-6) |
| Shock (power converter) | 15 g, 11 ms |
| Approvals | UL Listed per UL 508C, Class 10 overload protection |
| Standards | NEMA ICS, NFPA and IEC; manufactured under ISO 9001; AHRI certified |
| Weight | 52 lb (23.5 kg), varies with options |