QVRF-0R32-G

SKU: QVRF0R32G
$339.44

Call for Availability - (510) 636-7900

Details

Details

A2L Refrigerant Sensor, R-32, 0-50% LFL

Needs 24 VAC (15-24 VAC) or 24 VDC (18-30 VDC) power.

Cannot share an AC source with full-wave rectified devices without damage (half-wave rectifier on board).

Fits a standard two-gang electrical box or installs directly within an appliance.

Key Features

  • Relay operation: Relay 1 on above 20% LFL and off below 15% LFL; relay 2 on any fault
  • Digital output: RS-485, OptoMux or Modbus RTU
  • Sensor life: Approx. 12 years

Product Specifications

ManufacturerGreystone
ModelQVRF0R32G (QVRF-0R32-G)
RefrigerantR-32
Refrigerant classA2L
Factory calibration range0 to 50% LFL
Sensing element technologyNon-dispersive infrared (NDIR)
Sensor lifeApprox. 12 years
Accuracy / repeatability+/-2.5% LFL at 0 to 25% LFL (standard range); +/-5.0% LFL at 25 to 50% LFL (extended range)
Shelf lifeUnlimited
Response time30 seconds
Coverage area7500 sq ft (700 sq m); 50 ft (15 m) radius
Mounting height1 ft (0.3 m) above the floor
MountingStandard two-gang electrical box (IP54) or directly within an appliance
Power supply24 VAC (15-24 VAC); 24 VDC (18-30 VDC)
Power noteHalf-wave rectifier on board: mixing half-wave and full-wave rectified devices on the same AC source damages devices; a shared DC source is less problematic
Fuse0.750A polyswitch
Supply current0.4A max (normal working mode)
LED indicatorGreen blinking: normal, with communication; yellow flash: sensor fault; red flash: alarm and purge
Warm-up time30 minutes
Relay outputs2 SPDT (Form C) dry contacts; 1.0A max at 30 VDC, 0.3A max at 125 VAC (resistive load)
Relay operationRelay 1 on above 20% LFL and off below 15% LFL; relay 2 on any fault
Relay lifeMechanical 50 million, electrical 200,000 operations
Digital outputRS-485, OptoMux or Modbus RTU (default OptoMux, address 3, 4800 baud); connects to the Q4C-II Controller, M-Controller2, and Q-Controller
Buzzer50 dB at 10 cm, 2700 Hz; on when relay 1 is on
LocationIndoor use only
Operating temperature-40 to 158 deg F (-40 to 70 deg C)
Storage temperature-49 to 185 deg F (-45 to 85 deg C)
Ambient humidity5 to 95% RH, non-condensing
Operating pressureAtmospheric
EnclosureIP54 with splash guard
WiringTSP for power; Belden 984 for RS-485
StandardsASHRAE Standard 15; IEC 60335-2-40
Dimensions4.6 x 4.6 x 1.6 in. (116 x 116 x 40 mm)
WeightLess than 0.5 lb (0.23 kg)