CUL6438SR-CV1/U

SKU: CUL6438SRCV1

Call for Availability - (510) 636-7900

Details

Details

Controlco Product Information Tabs
Product DetailsSpecificationsDownloads

Product Information


Stryker LON Configurable CVAHU Controller: 6 UI: 4 DI: 3 AO: 8 Relay DO


The CUL6438SR-CV1, CVL4022AS-VAV1, and CVL4024NS-VAV1 controllers are part of the Stryker family. The controllers are Free Topology Transceiver (FTT) LONMARK®-certified devices designed to control HVAC equipment.


These controllers provide many options and advanced system features that allow state-of-the-art commercial building control. Each controller is configurable using the NIAGARA FRAMEWORK® software.


The Stryker controllers require the Stryker Feature to be licensed in the WEBpro workbench tool and the WEBS AX JACE Controller for programming and downloading any brand of the Niagara Workbench or JACE controller.


The controllers are for use in VAV (Variable Air Volume) and CVAHU (Constant Volume Air Handling Unit) control applications. Each controller contains a host microcontroller to run the main HVAC application and a second microcontroller for LONWORKS® network communications.


Each controller provides flexible, universal inputs for external sensors, digital inputs, and a combination of analog outputs and digital outputs.


Features


  • Uses the Echelon® LONWORKS® network protocol.
  • Free Topology Transceiver (FTT) high-speed 78 kilobit communications network.
  • Capable of stand-alone operation, but can also use LONWORKS® Bus network communications.
  • Sylk™ bus for use with Sylk-enabled sensors.
  • 120 controllers per Q7751A,B Router when configured as a repeater.
  • Field configurable for control, input, and output functions using the NIAGARA FRAMEWORK® software.
  • Built-in Zone Control functions include a remote wall module interface and a scheduler.
  • Pressure-independent or pressure-dependent single VAV control (CVL4022AS-VAV1 and CVL4024NS-VAV1 only).
  • Microbridge air flow sensor with dual integral restrictor design.
  • Easy user access to air flow sensor inputs.
  • Actuator (CVL4022AS-VAV1 only) mounts directly onto VAV box damper shaft and has up to 44 lb-in (5 Nm) torque, 90-degree stroke, and 90 second timing at 60 Hz.
  • All wiring connections are made to removable terminal blocks to simplify controller installation and replacement.
  • Both controller housing and actuator are UL plenum rated.

Specifications


The configurable VAV/Unitary controllers are available as described in Table 1.


Controller Configurations


Controller ModelProgrammable TypeUniversal Inputs (UI)Digital Inputs (DI)Analog Outputs (AO)Digital Outputs (DO)Velocity Pressure Sensor (Microbridge)Series 60 Floating Actuator
CUL6438SR-CV1CVAHU6438 RelayNONO
CVL4022AS-VAV1VAV4022YESYES
CVL4024NS-VAV1VAV4024YESNO


Electrical


Rated Voltage:20-30 Vac
50/60 Hz
Power consumption100 VA for controller and all connected loads (including actuator on model CVL4022AS-VAV1)
Controller only load: 5 VA maximum (models CVL4024NS-VAV1 and CUL6438SR-CV1)
Controller and actuator load: 9 VA maximum (model CVL4022AS-VAV1)
External Sensors Power Output: 20 Vdc ±10% @ 75 mA maximum


Environmental


VAV Operating & Storage Temperature Ambient Rating
(Models CVL4022AS-VAV1 and CVL4024NS-VAV1)

  • Minimum: 32°F (0°C)
  • Maximum: 122°F (50°C)

CVAHU Operating & Storage Temperature Ambient Rating
(Model CUL6438SR-CV1)

  • Minimum: −40°F (−40°C)
  • Maximum: 150°F (65.5°C)
  • Relative Humidity:5% to 95% non-condensing

Real Time Clock


Operating Range:24-hour, 365-day, multi-year calendar including day of week and automatic daylight savings configuration.
Power failure backup:24 hours at 32° to 100°F (0° to 38°C)
22 hours at 100° to 122°F (38° to 50°C)
Accuracy±1 minute per month at 77°F (25°C)


Velocity Pressure Sensor (Models CVL4022AS-VAV1 and CVL4024NS-VAV1)


  • Operating Range: 0 to 1.5 in. H₂O (0 to 374 Pa)

Series 60 Floating Actuator (Model CVL4022AS-VAV1)


Rotation Stroke:95° ± 3° for CW or CCW opening dampers
Torque Rating:44 lb-in. (5 Nm)
Run time for 90° rotation: 90 sec at 60 Hz


Inputs and Outputs


Each controller has a combination of universal inputs (UI), digital inputs (DI), analog outputs (AO), and digital outputs (DO) as listed in Table 1.

Digital Input (DI) Circuits


Voltage rating: 0 to 30 Vdc open circuit
Input type:Dry contact to detect open and closed circuit
Operating range:Open circuit = False; Closed circuit = True
Resistance:Open circuit > 3,000 Ohms
Closed circuit < 500 Ohms


Digital Triac Output (DO) Circuits


  • Voltage Rating: 20 to 30 Vac @ 50–60 Hz
  • Current Rating: 25 mA to 500 mA continuous

Digital Relay Output (DO) Circuits (CUL6438SR-CV1 Only)

  • Voltage Rating: 20 to 30 Vac @ 50–60 Hz
  • Current Rating: 0 mA to 1 A continuous

Analog Output (AO) Circuits

Analog outputs can be individually configured for current or voltage.


Analog Current Outputs

  • Current Output Range: 4.0 to 20.0 mA
  • Output Load Resistance: 550 Ohms maximum

Analog Voltage Outputs

  • Voltage Output Range: 0 to 10.0 Vdc
  • Maximum Output Current: 10.0 mA

Universal Input (UI) Circuits


Input TypeSensor TypeOperating Range
Room / Zone / Discharge / Outdoor Air Temperature20K Ohm NTC-40°F to 199°F (-40°C to 93°C)
Outdoor Air TemperatureC7031G-40°F to 120°F (-40°C to 49°C)
Outdoor Air TemperatureC7041F-40°F to 250°F (-40°C to 121°C)
Temperature SensorPT1000 (IEC751 3850)-40°F to 199°F (-40°C to 93°C)
Setpoint PotentiometerTR23 (500–10,500 Ohm) -4° DDC to 4° DDC (-8° DDF to 7° DDF)
or 50°F to 90°F (10°C to 32°C)
Resistive InputGeneric 100 Ohms – 100K Ohms
Voltage InputTransducer / Controller0–10 Vdc
Discrete InputDry Contact Closure Open Circuit ≥ 3000 Ohms
Closed Circuit < 3000 Ohms


Hardware


Each controller uses a Texas Instruments MSP430 family microprocessor. The processor contains on-chip FLASH program memory, FLASH information memory, and RAM.


Memory Capacity


  • Flash Memory:116 KB with 8 KB available for user program
  • Retains FLASH settings for up to 10 years
  • RAM: 8 KB
Integrated Actuator Specifications