TR42
Details
Details
TR42 Sylk LCD Wall Module, Temperature, Setpoint, Override, Fan
Works with Sylk-enabled Spyder and ComfortPoint Open controllers; not compatible with Stryker controllers.
Needs 2 wires: Sylk carries power and communication.
Setpoint, override, and fan options are configured in the controller tool.
Key Features
- Temperature sensing
- LCD display
- Setpoint, override, fan
- Sylk, 2-wire
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | TR42 |
| Product type | Sylk wall module with display |
| Sensing | Temperature |
| Display | LCD; deg F or deg C |
| Setpoint | Relative warmer-cooler or absolute; range limits adjustable |
| Override | Network time or 1-24 hours |
| Fan control | Auto-On, Auto-Off-On, or Auto-Off-Low-Med-High (not on ComfortPoint Open VAV) |
| Communication | Sylk, 2-wire, polarity insensitive |
| Power | From the Sylk bus |
| Fits | Sylk-enabled Spyder controllers (date code 1220 or later), Spyder Micro BACnet, ComfortPoint Open controllers, CPO-VAV2A |
| Max per controller | 3 on ComfortPoint Open; Spyder limits per the Sylk capacity tool |
| Accuracy | +/-0.36 deg F at 77 deg F |
| Setpoint limit | 50-149 deg F (10-65 deg C), Spyder only |
| Operating temperature | 32-125 deg F (0-52 deg C) |
| Shipping temperature | -40 to 150 deg F (-40 to 65.5 deg C) |
| Humidity | 5-95% non-condensing |
| Accessories | 50007298-001 cover plate, 6-7/8 x 5 in., pack of 12 |
| Approvals | CE; UL94-V0 enclosure; FCC Part 15 Class B |
| Honeywell form | 63-1389-04 Rev. 7-24 |