HRC2LT2PS

SKU: HRC2LT2PS
$262.27

Call for Availability - (510) 636-7900

Details

Details

Room RH Transmitter, +/-2% RH, 100 ohm Plat RTD, Setpoint, Override, LCD

Needs 24 VAC/DC power.

Includes a passive temp element on its own two terminals.

Key Features

  • Output: 4-20mA, 0-5V, or 0-10V, field selectable
  • Setpoint: 0-10k slide pot
  • Override: momentary NO pushbutton
  • Display: 3-digit LCD, 00.0 to 99.9% RH

Product Specifications

ManufacturerGreystone
ModelHRC2LT2PS
RH sensorThermoset polymer based capacitive
RH accuracy+/-2% RH (5 to 95% RH)
RH range0 to 100% RH
Resolution0.01% RH
Hysteresis+/-0.8% RH at 77 deg F (25 deg C)
Response time8 seconds typical
Stability<0.25% RH/year
Output4-20mA, 0-5V, or 0-10V, field selectable; scaled 0-100% RH
Output drive at 24 VDCCurrent: 550 ohm maximum; voltage: 10,000 ohm minimum
Power supply24 VAC/DC +/-10% typical, 28 VAC/DC maximum
Consumption20 mA at 24 VDC
Temp sensor100 ohm platinum RTD, IEC 751, 385 alpha, thin film; 2-wire resistance output
Setpoint0-10k slide pot, front panel; 2-wire resistance output
OverrideMomentary NO pushbutton, front panel; SPST, 50 mA at 12 VDC
Display3-digit LCD, 00.0 to 99.9% RH; 1.5 x 0.65 in. (38.1 x 16.5 mm) window, 0.45 in. digits
Operating conditions32 to 122 deg F (0 to 50 deg C)
EnclosureWhite ABS, UL94-V0, IP30 (NEMA 1)
Dimensions3.3 x 4.7 x 1.15 in. (84 x 119 x 29 mm), W x H x D
MountingSingle gang electrical box or wall
Wiring connectionsScrew terminal block, 14 to 22 AWG
Country of originCanada