HATXRC18A2P1
Details
Details
Room Temp Transmitter, 4-20mA, 32 to 122 deg F, Custom 20-30k Setpoint, Class A RTD
Ships as a custom build, with the 20-30k setpoint slide pot made to order.
Runs on 15-35 VDC loop power or 22-32 VAC.
Key Features
- Sensor accuracy: +/-0.27 deg F
Product Specifications
| Manufacturer | Greystone |
|---|---|
| Model | HATXRC18A2P1 |
| Sensor | 1000 ohm platinum RTD, IEC 751, 385 alpha, thin film, Class A |
| Sensor accuracy | +/-0.27 deg F (+/-0.15 deg C) @ 32 deg F (0 deg C) |
| Output | 4-20mA current loop (factory configured) |
| Scaled range | 32 to 122 deg F (0 to 50 deg C) |
| Transmitter accuracy | +/-0.1% of span, including linearity |
| Internal adjustment | Zero and span pots |
| Power supply | 15-35 VDC (loop-powered) or 22-32 VAC |
| Minimum loop current | 2 mA nominal (occurs with shorted sensor) |
| Maximum loop current | 22.4 mA nominal |
| Maximum loop load | >600 ohm |
| Input voltage effect | Negligible over specified operating range |
| RFI rejection | Good RFI rejection of normal frequencies |
| Protection circuitry | Reverse voltage protected and output limited |
| Setpoint | Front panel slide pot, 2-wire resistance output, 20-30k ohm, custom (made on request) |
| Operating conditions | 32 to 140 deg F (0 to 60 deg C), 0 to 95% RH, non-condensing |
| Enclosure | White ABS, IP30 (NEMA 1) |
| Enclosure dimensions | 3.3 in. W x 4.6 in. H x 1.15 in. D (84 x 117 x 29 mm) |
| Wiring connections | Screw terminal block (14 to 22 AWG) |
| Mounting | Single-gang electrical box or directly to the wall; insulating foam backing |
| Country of origin | Canada |