HATXDCE48IA006
Details
Details
Copper Averaging Duct Temp Transmitter, 6 ft, 4-20mA, 1/3 DIN RTD
Runs on 15-35 VDC loop power or 22-28 VAC.
Key Features
- Sensing points: 4
- Sensor accuracy: +/-0.18 deg F
- Probe sensing range: -4 to 140 deg F
- Enclosure: ABS, UL94-V0, IP65 (NEMA 4X), with thread adapter (1/2 in. NPT to M16) and cable gland fitting
Product Specifications
| Manufacturer | Greystone |
|---|---|
| Model | HATXDCE48IA006 |
| Sensor | 1000 ohm platinum RTD, IEC 751, 385 alpha, thin film, 1/3 DIN |
| Sensor accuracy | +/-0.18 deg F (+/-0.1 deg C) @ 32 deg F (0 deg C) |
| Probe sensing range | -4 to 140 deg F (-20 to 60 deg C) |
| Wire | FT-6 rated plenum cable, 22 AWG |
| Probe material | Soft copper |
| Probe diameter | 0.315 in. (7.94 mm) |
| Averaging length | 6 ft (1.8 m) |
| Sensing points | 4 |
| Output | 4-20mA current loop (factory configured) |
| Transmitter accuracy | +/-0.1% of span, including linearity |
| Calibration | Factory calibrated; field adjustment voids the warranty |
| Input voltage effect | Negligible over specified operating range |
| Protection circuitry | Reverse voltage protected and output limited |
| Ambient operating range | -40 to 140 deg F (-40 to 60 deg C), 5 to 95% RH non-condensing |
| Enclosure | ABS, UL94-V0, IP65 (NEMA 4X), with thread adapter (1/2 in. NPT to M16) and cable gland fitting |
| Enclosure dimensions | 3.25 x 2.75 x 2.05 in. (82.5 x 69.8 x 52.0 mm) |
| Termination | Terminal block (14 to 22 AWG) |
| Protection class | III |
| Power supply | 15-35 VDC (loop-powered) or 22-28 VAC Limited Energy, <15 W |
| Consumption | 20 mA |
| EU conformity | CE |
| Certification | UL 60730 and CSA E60730 |
| Plenum rating | UL 2043 / CSA / ULC S142: suitable for use in air handling spaces per NEC Section 300.22(C) |
| Purpose of control | Operating control |
| Type of action | Type 1 |
| Impulse voltage | 330 V |
| Pollution degree | 2 |
| Country of origin | Canada |