GW-1000-NWE
Details
Details
GW-1000-NWE RBM Express Wireless Gateway, North America
Works as a component of the Remote Building Manager Express system; configured from the mobile app, with over-the-air updates.
Works with TC500A-N thermostats and IO-10MIXR-NWE Smart IO devices over secured BACnet.
Has an SMA connector for its external Wi-Fi/Bluetooth antenna; the RS-485, USB, and RJ11 ports and Bluetooth are for future use.
Runs on 24 VAC or 24 VDC.
Key Features
- 2 Ethernet ports
- Wi-Fi access point, 12 devices
- 3000 points max
- North American RF conformance
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | GW-1000-NWE |
| Product type | Wireless gateway (Remote Building Manager Express) |
| Region | North American RF conformance (NWE); GW-1000-WE covers Europe and Latin America |
| Ethernet | 2 RJ45, 10/100/1000BASE-T: Ethernet 1 internet/cloud, Ethernet 2 LoRaWAN hub |
| Wireless | Wi-Fi access point 802.11b/g/n with auto channel selection (5 GHz for future use), 100 ft range line of sight; Bluetooth 4.2 (future use); SMA antenna connector for an external antenna |
| Wi-Fi devices | 12 max |
| Protocol | BACnet (secured), HTTPS, MQTTS, DHCP |
| Capacity | 3000 points max; 2 days trend retention (1 min samples); 70,000 alarm records |
| Clock | Real-time clock, 72-hour retention |
| Future-use ports | 5 RS-485, micro USB, USB Type A, RJ11 |
| Supply power | 19-29 VAC 50/60 Hz or 19-29 VDC; NEC Class 2 transformer |
| Power consumption | 35 VA max at 24 VAC (1430 mA); 15 W max at 24 VDC (620 mA) |
| Operating temperature | 32 to 122 deg F (0 to 50 deg C) |
| Storage temperature | -20 to 158 deg F (-28.9 to 70 deg C) |
| Humidity | 5-95% RH non-condensing |
| Protection | IP20 |
| Mounting | 35 mm DIN rail (horizontal or vertical) or wall/panel with four screws; DIN43880 enclosures, 45 mm max slot height |
| Dimensions | 5.744 x 4.331 x 2.047 in. (145.8 x 110 x 52 mm) |
| Accessories | GW-TCVR and GW-EXT-TCVR terminal covers, ANT-REM remote antenna, GW-ANT-LOC local antenna (each pack of 4) |
| Approvals | UL 60730-1; UL 916; CAN/CSA-E60730-1; EN 60730-1; EN 60730-2-9; FCC Part 15 Subpart B; CAN ICES-3 (B)/NMB-3(B); BQB; RoHS II; REACH |
| Honeywell form | 31-00424-01 Rev. 05-23; 31-00425-01 Rev. 05-23; 31-00426-01 Rev. 05-23 |