G350B-N+SVKX24-MFT
Details
Details
G350B-N+SVKX24-MFT 2 in. 3-Way Globe Valve with Electronic Fail-Safe Actuator, 24 VAC/DC, MFT
Mixes or diverts chilled or hot water, up to 60% glycol, in an ANSI Class 250 bronze body with NPT ends.
Ships set for 2-10 VDC control and feedback; ZTH US sets other VDC ranges, PWM, on/off, or floating, and a ZG-R01 500 ohm resistor allows 4-20mA.
Drives the valve to its fail-safe position on power loss after a 2 s delay; a switch reverses the fail direction.
Key Features
- Cv: 41
- Actuating force motor: 340 lb (1500 N)
- Running time motor variable: 35 to 150 s
Product Specifications
| Manufacturer | Belimo |
|---|---|
| Model | G350BNSVKX24MFT (G350B-N+SVKX24-MFT) |
| Valve | G350B-N |
| Valve Size | 2" (50) |
| Fluid | chilled or hot water, up to 60% glycol |
| Fluid Temp Range (water) | 20 to 280 deg F (-7 to 138 deg C) |
| Body Pressure Rating | ANSI Class 250, up to 400 psi below 150 deg F |
| Flow characteristic | modified equal percentage, linear B to AB |
| Valve servicing | repack kits available |
| Rangeability Sv | A-port 100:1, B-port 50:1 |
| Flow Pattern | 3-way Mixing/Diverting |
| Leakage rate | ANSI Class VI |
| Controllable flow range | stem up - open B to AB |
| Cv | 41 |
| Valve body | Bronze |
| Valve plug | brass |
| Spindle | stainless steel |
| Spindle seal | EPDM O-ring |
| Seat | Bronze |
| Pipe connection | NPT female ends |
| Suitable actuators, non-spring return | SVB(X) |
| Suitable actuators, spring return | AF |
| Suitable actuators, electronic fail-safe | SVKB(X) |
| Valve weight | 8.8 lb |
| Actuator | SVKX24-MFT |
| Nominal voltage | AC/DC 24 V |
| Nominal voltage frequency | 50/60 Hz |
| Power consumption in operation | 3 W |
| Power consumption in rest position | 2 W |
| Transformer sizing | 7 VA (class 2 power source) |
| Electrical Connection | 18 GA plenum cable, 3 ft (1 m), with 1/2" conduit connector, degree of protection NEMA 2 / IP54 |
| Overload Protection | electronic throughout full stroke |
| Electrical Protection | actuators are double insulated |
| Actuating force motor | 340 lb (1500 N) |
| Operating range Y | 2 to 10 V |
| Operating range Y note | 4 to 20 mA w/ ZG-R01 (500 ohm, 1/4 W resistor) |
| Input Impedance | 100,000 ohm for 2 to 10 V (0.1 mA), 500 ohm for 4 to 20 mA, 1,500 ohm for PWM, On/Off and Floating point |
| Operating range Y variable | Start point 0.5 to 30 V, End point 2.5 to 32 V |
| Options positioning signal | variable (VDC, PWM, on/off, floating point) |
| Position feedback U | 2 to 10 V |
| Position feedback U note | Max. 0.5 mA |
| Position feedback U variable | VDC variable |
| Bridging time (PF) | 2 s |
| Pre-charging time | 5 to 20 s |
| Direction of motion motor | selectable with switch |
| Direction of motion fail-safe | reversible with switch |
| Manual override | 4 mm hex crank (shipped w/actuator) |
| Stroke | 0.75" (19 mm) |
| Running Time (Motor) | 90 s |
| Running time motor variable | 35 to 150 s |
| Running time fail-safe | <35 s |
| Noise level, motor | 45 dB(A) |
| Noise level, fail-safe | 60 dB(A) |
| Position indication | Mechanically, with pointer |
| Degree of protection IEC/EN | IP54 |
| Degree of protection NEMA/UL | NEMA 2, UL Enclosure Type 2 |
| Agency Listing | cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU |
| Quality Standard | ISO 9001 |
| Ambient temperature | -22 to 122 deg F (-30 to 50 deg C) |
| Storage temperature | -40 to 176 deg F (-40 to 80 deg C) |
| Ambient humidity | Max. 95% RH, non-condensing |
| Actuator servicing | maintenance-free |
| Actuator weight | 3.53 lb (1.6 kg) |
| Housing material | Die cast aluminium and plastic casing |
| Parallel operation | Allowed; observe power consumption and input impedance |