E50-600200-J05SCS-NS
Details
Details
E50-600200-J05SCS-NS E-Mon Class 5000 Smart Meter, 200A, 347/600V, BACnet IP
Measures 3-phase, 4-wire circuits at 347/600V.
Talks EZ7 on its RS-485 port and BACnet IP on its Ethernet port.
Current sensors are not included; order 3 solid-core 0-2V sensors rated 200A.
Key Features
- 200A rating
- +/-0.2% accuracy
- Current sensors not included
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | E50-600200-J05SCS-NS |
| Product type | kWh/demand smart meter with communication, E-Mon Class 5000 |
| Service voltage | 347/600V |
| Phase and wiring | 3-phase, 4-wire |
| Amperage rating | 200A |
| Current sensors | Not included (order 3 solid-core 0-2V sensors separately) |
| Sensor cable run | Up to 500 ft from the meter |
| Display | 4-line LCD: kWh, kW demand with peak date and time, power factor per phase, real-time kW, amps and volts per phase |
| Interval data | kWh and kVARh delivered and received; 15-minute intervals for up to 72 days or 5-minute intervals for up to 24 days; not available via BACnet |
| RS-485 port | EZ7 |
| Ethernet port | BACnet IP |
| Daisy chain | Up to 52 devices per RS-485 EZ7 channel; 3-conductor 22 AWG, up to 4,000 ft total |
| Inputs and outputs | Two pulse inputs (channels 5 and 6), two pulse outputs, phase loss alarm contact (NO) |
| Enclosure | JIC steel, padlocking hasp and mounting flanges, indoor |
| Accuracy | ANSI C12.20, +/-0.2% from 1% to 100% of rated load |
| Approvals | UL/cUL listed; CE; BACnet BTL certified |
| Honeywell form | 38-00068-01 |