E34-6001600R06XSPKIT-NS
Details
Details
E34-6001600R06XSPKIT-NS E-Mon Class 3400 kWh/Demand Meter, 1600A, 347/600V, Modbus RTU and TCP/IP, Expanded
Set up for single-phase, 3-wire service at 347/600V.
Talks Modbus RTU on its RS-485 port and Modbus TCP/IP on its Ethernet port.
Current sensors are not included; order 2 split-core 0-2V sensors rated 1600A.
Adds load control, two external meter inputs, and kWh and kVARh pulse outputs (expanded feature package).
Key Features
- 1600A rating
- +/-0.2% accuracy
- Expanded feature package
- Current sensors not included
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | E34-6001600R06XSPKIT-NS |
| Product type | Advanced kWh/demand meter with communication, E-Mon Class 3400 |
| Service voltage | 347/600V |
| Phase and wiring | Single-phase, 3-wire |
| Amperage rating | 1600A |
| Current sensors | Not included (order 2 split-core 0-2V sensors separately) |
| Sensor cable run | Up to 500 ft from the meter |
| Display | 4-line by 20-character backlit LCD: kWh, kW demand with peak date and time, power factor per phase, real-time kW, amps and volts per phase |
| Interval data | kWh and kVARh delivered and received; 15-minute intervals for up to 72 days or 5-minute intervals for up to 24 days; not available via BACnet |
| RS-485 port | Modbus RTU |
| Ethernet port | Modbus TCP/IP |
| Daisy chain | Up to 52 devices per RS-485 EZ7 channel; 3-conductor 22 AWG, up to 4,000 ft total |
| Expanded features | Load control/shedding; two external meter inputs (channels 5 and 6); two pulse outputs (one kWh, one kVARh) |
| Enclosure | NEMA 4X polycarbonate, padlocking hasp, mounting flanges, indoor/outdoor; one 1-1/16 in. knockout |
| Accuracy | ANSI C12.20, +/-0.2% from 1% to 100% of rated load; meets MID accuracy standards |
| Approvals | UL/cUL listed |
| Dimensions | 8 x 6 x 3-3/4 in. (H x W x D) |
| Honeywell form | 38-00067-01 |