E34-600100-R03-X-SCS
Details
Details
E34-600100-R03-X-SCS E-Mon Class 3400 kWh/Demand Meter, 100A, 347/600V, BACnet MS/TP, Expanded
Measures 3-phase, 3-wire (delta) or 4-wire (wye) circuits at 347/600V.
Talks BACnet MS/TP on its RS-485 port and EZ7 Ethernet on its Ethernet port.
Ships with 3 solid-core 0-2V current sensors rated 100A.
Adds load control, two external meter inputs, and kWh and kVARh pulse outputs (expanded feature package).
Key Features
- 100A rating
- +/-0.2% accuracy
- Expanded feature package
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | E34-600100-R03-X-SCS |
| Product type | Advanced kWh/demand meter with communication, E-Mon Class 3400 |
| Service voltage | 347/600V |
| Phase and wiring | 3-phase (3-wire delta or 4-wire wye) |
| Amperage rating | 100A |
| Current sensors | 3 solid-core, 0-2V output, included |
| Sensor cable run | Up to 500 ft from the meter |
| Display | 4-line by 20-character backlit LCD: kWh, kW demand with peak date and time, power factor per phase, real-time kW, amps and volts per phase |
| Interval data | kWh and kVARh delivered and received; 15-minute intervals for up to 72 days or 5-minute intervals for up to 24 days; not available via BACnet |
| RS-485 port | BACnet MS/TP |
| Ethernet port | EZ7 Ethernet |
| Daisy chain | Up to 52 devices per RS-485 EZ7 channel; 3-conductor 22 AWG, up to 4,000 ft total |
| Expanded features | Load control/shedding; two external meter inputs (channels 5 and 6); two pulse outputs (one kWh, one kVARh) |
| Enclosure | NEMA 4X polycarbonate, padlocking hasp, mounting flanges, indoor/outdoor; one 1-1/16 in. knockout |
| Accuracy | ANSI C12.20, +/-0.2% from 1% to 100% of rated load; meets MID accuracy standards |
| Approvals | UL/cUL listed; BACnet BTL certified; MV-90 compatible (EZ7 only) |
| Dimensions | 8 x 6 x 3-3/4 in. (H x W x D) |
| Honeywell form | 38-00067-01 |