E34-480100-R02-SPSCS-NS
Details
Details
E34-480100-R02-SPSCS-NS E-Mon Class 3400 kWh/Demand Meter, 100A, 277/480V, Modbus RTU
Set up for single-phase, 3-wire service at 277/480V.
Talks Modbus RTU on its RS-485 port and EZ7 Ethernet on its Ethernet port.
Current sensors are not included; order 2 solid-core 0-2V sensors rated 100A.
Key Features
- 100A rating
- +/-0.2% accuracy
- Current sensors not included
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | E34-480100-R02-SPSCS-NS |
| Product type | Advanced kWh/demand meter with communication, E-Mon Class 3400 |
| Service voltage | 277/480V |
| Phase and wiring | Single-phase, 3-wire |
| Amperage rating | 100A |
| Current sensors | Not included (order 2 solid-core 0-2V sensors separately) |
| Sensor cable run | Up to 500 ft from the meter |
| Display | 4-line by 20-character backlit LCD: kWh, kW demand with peak date and time, power factor per phase, real-time kW, amps and volts per phase |
| Interval data | kWh and kVARh delivered and received; 15-minute intervals for up to 72 days or 5-minute intervals for up to 24 days; not available via BACnet |
| RS-485 port | Modbus RTU |
| Ethernet port | EZ7 Ethernet |
| Daisy chain | Up to 52 devices per RS-485 EZ7 channel; 3-conductor 22 AWG, up to 4,000 ft total |
| Enclosure | NEMA 4X polycarbonate, padlocking hasp, mounting flanges, indoor/outdoor; one 1-1/16 in. knockout |
| Accuracy | ANSI C12.20, +/-0.2% from 1% to 100% of rated load; meets MID accuracy standards |
| Approvals | UL/cUL listed; MV-90 compatible (EZ7 only) |
| Dimensions | 8 x 6 x 3-3/4 in. (H x W x D) |
| Honeywell form | 38-00067-01 |