E32-208100-MRTU-SPKIT E-Mon Class 3200 kWh/Demand Meter, 100A, 120/208-240V, 2-Element, Modbus RTU, MMU
Set up for single-phase or two-phase service at 120/208-240V as a 2-element meter.
Talks Modbus RTU on its RS-485 port.
Ships with 2 split-core 0-2V current sensors rated 100A.
Mounts in an MMU multiple meter unit cabinet, ordered separately.
Key Features
- 100A rating
- Modbus RTU
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | E32-208100-MRTU-SPKIT |
| Product type | Advanced kWh/demand meter with communication, E-Mon Class 3200 |
| Service voltage | 120/208-240V |
| Phase and wiring | Single-phase or two-phase, 2-element (-SP option; phase B to C jumper factory installed) |
| Amperage rating | 100A |
| Current sensors | 2 split-core, 0-2V output, included |
| Sensor cable run | Up to 500 ft from the meter |
| Display | 4-line LCD: kWh delivered, peak kW demand with date and time, actual kW load, average amps and volts per phase, phase-to-phase volts, power factor per phase |
| RS-485 port | Modbus RTU |
| Daisy chain | 3-conductor 22-26 AWG, up to 4,000 ft; 64 nodes including master; 9600 to 76800 baud |
| Input power | 6 VA maximum |
| Line frequency | 50-60 Hz |
| Enclosure | MMU style for an E-Mon MMU multiple meter unit cabinet; indoor only |
| Accuracy | ANSI C12.20 |
| Operating temperature | -20 to 50 deg C (-4 to 122 deg F) |
| Humidity | 0-95% non-condensing |
| Approvals | EN 61326-1:2006; IEC 61010-1:2001 |
| Honeywell form | 62-0390-04; 38-00077-01; 38-00071-01 |