CS-425-HC-10

SKU: CS425HC10
$56.29

Call for Availability - (510) 636-7900

Details

Details

Current Switch with Triac Output, 1 A Trip, 120 VAC 2.5 A, 10 Minute Off Delay

Switches a 120 VAC load up to 2.5 A (such as a dryer vent booster fan) through its triac when the monitored line draws about 1 A.

Powers itself from the monitored line; no adjustment needed.

Holds the output closed for 10 minutes after the current drops.

Key Features

  • Maximum core current: 50 A

Product Specifications

ManufacturerGreystone
ModelCS425HC10 (CS-425-HC-10)
Maximum core current50 A
Operating temperature32 to 104 deg F (0 to 40 deg C)
Trip set-pointApproximately 1 A, factory set
Time delay10 minutes (output stays closed after current drops)
Enclosure size1.95 x 3.45 x 1 in. H x W x D (49 x 87 x 25 mm)
AC conductor hole0.8 in. (20 mm) diameter
Switch rating120 VAC @ 2.5 A maximum
Switch typeSolid-state triac, NO
Off-state leakage<1 mA
Turn on time<200 ms
Operating humidity0 to 95 %RH non-condensing
MaterialABS, UL94-V0, insulation class 600V
Mounting holes2 x 0.19 in. holes spaced 3 in. on base (2 x 5 mm spaced 76 mm)
Agency approvalscULus listed