CDDTF2R02

SKU: CDDTF2R02
$627.48

Call for Availability - (510) 636-7900

Details

Details

Duct CO2 Transmitter, 0-20,000 ppm, 4-20mA/0-5V/0-10V, 100 ohm Plat RTD Temp, Relay, Cable Gland Fitting

Needs 20 to 28 VAC/DC power.

Key Features

  • Output signal: 4-20mA active (sourcing) or 0-5V/0-10V, field selectable
  • Relay: Form A (NO), 2A @ 140 VAC, 2A @ 30 VDC

Product Specifications

ManufacturerGreystone
ModelCDDTF2R02
Gas detectedCarbon dioxide (CO2)
Measurement typeDual channel non-dispersive infrared (NDIR), diffusion sampling
Measurement range0 to 20,000 ppm, programmable span
Standard accuracy+/-75 ppm (400 to 1000 ppm); 10% of reading above 1000 ppm
Temperature dependence0.11% FS per deg F (0.2% FS per deg C)
StabilityUnder 5% FS over life of sensor (10 years typical)
Pressure dependence0.13% of reading per mm Hg
Altitude correctionProgrammable 0 to 5000 ft via keypad
Response timeUnder 2 minutes for 90% step change, typical
Warm-up timeUnder 2 minutes
Power supply20 to 28 VAC/DC (non-isolated half-wave rectified)
Current consumption4-20mA output: 120 mA max @ 24 VDC, 212 mA max @ 24 VAC
Output signal4-20mA active (sourcing) or 0-5V/0-10V, field selectable
Output drive capabilityCurrent: 550 ohm max; voltage: 5k ohm min
Output resolution10 bit PWM
Input voltage effectNegligible over specified operating range
Protection circuitryReverse voltage and overvoltage protected
LCDBacklit (enable or disable via keypad); 1 ppm CO2 resolution; 1.4 x 0.6 in. (35 x 15 mm)
Temp sensor100 ohm platinum RTD, IEC 751, 385 alpha, thin film; 2-wire resistive output
RelayForm A (NO), 2A @ 140 VAC, 2A @ 30 VDC; trip point and hysteresis programmable via keypad
Wiring connectionsScrew terminal block (14 to 22 AWG)
EnclosureIP65 (NEMA 4X) polycarbonate, hinged and gasketed cover; thread adapter (1/2 in. NPT to M16) and cable gland fitting included
DimensionsEnclosure 4.585 x 4.43 x 2.11 in. (116.5 x 112.5 x 53.7 mm); probe 6 in. (152 mm) long, 0.88 in. (22.5 mm) diameter, 0.5 in. NPT
MountingOutside of a return air duct with the sampling tube inserted; straight duct at least 5 ft from corners
ApprovalsCE, RoHS
Country of originCanada

Product Resources