CDD4B101T2RS

SKU: CDD4B101T2RS
$611.71

Call for Availability - (510) 636-7900

Details

Details

Room CO2 Transmitter, 0-20,000 ppm, 4-20mA/0-5V/0-10V, 100 ohm Plat RTD Temp, Relay, Override, Viewable LCD

Needs 20 to 28 VAC/DC power.

Key Features

  • Output signal: 4-20mA active (sourcing), 0-5V, or 0-10V, field selectable
  • Relay: Form A (NO), 2A @ 140 VAC/30 VDC
  • Override switch: Front panel pushbutton, NO SPST

Product Specifications

ManufacturerGreystone
ModelCDD4B101T2RS
Gas detectedCarbon dioxide (CO2)
Sensor typeDual wavelength non-dispersive infrared (NDIR)
Sensor accuracy+/-75 ppm or 10% of reading, whichever is greater
Measurement range0 to 20,000 ppm standard, programmable span 2000 to 20,000 ppm
Pressure dependencyUnder 0.13% of reading per mm Hg
Temperature dependency0.11% FS per deg F (0.2% FS per deg C)
StabilityUnder 5% FS over life of sensor (15 years typical)
Altitude correctionProgrammable 0 to 5000 ft via keypad
Response timeUnder 2 minutes for 90% step change, typical
Sensor coverage area1,000 sq ft (100 sq m) typical
Power supply20 to 28 VDC/VAC (non-isolated half-wave rectified)
Protection circuitryReverse voltage and overvoltage protected
Output signal4-20mA active (sourcing), 0-5V, or 0-10V, field selectable
Current consumption100 mA max @ 24 VDC, 185 mA max @ 24 VAC with all options
Output drive capabilityCurrent: 550 ohm max; voltage: 5k ohm min
Ambient operating range32 to 122 deg F (0 to 50 deg C), 0 to 95% RH non-condensing
LCDViewable; 1 ppm CO2 resolution; 1.4 x 0.6 in. (35 x 15 mm), 2-line x 8 character; backlight enable or disable via keypad
Temp sensor100 ohm platinum RTD, IEC 751, 385 alpha, thin film; 2-wire resistive output
RelayForm A (NO), 2A @ 140 VAC/30 VDC; trip point programmable 500 to 15,000 ppm, hysteresis 25 to 500 ppm
Override switchFront panel pushbutton, NO SPST, 50 mA @ 12 VDC
Wiring connectionsScrew terminal block (14 to 22 AWG)
EnclosureWhite ABS, IP30 (NEMA 1); 3.3 x 4.7 x 1.15 in. (84 x 119 x 29 mm)
MountingSingle-gang electrical box or directly on a wall
Calibration guarantee5 years for CO2-based ventilation control where the ACLP self-calibration can operate (Greystone terms)
Country of originCanada

Product Resources