CD2RMCC02XSXXX

SKU: CD2RMCC02XSXXX
$364.74

Call for Availability - (510) 636-7900

Details

Details

Room CO2 Transmitter, 0-2000 ppm, 4-20mA/0-5V/0-10V, 100 ohm Plat RTD Temp, Override, Concealed LCD

Needs 24 VAC/DC power. Needs self-calibration turned off and a yearly calibration in spaces occupied 24 hours.

Key Features

  • Output signal: 4-20mA (3-wire), 0-5V, or 0-10V, field selectable
  • Override switch: Dry contact, 50 mA @ 12 VDC max
  • Sensor coverage area: 1,000 sq ft (100 sq m) typical

Product Specifications

ManufacturerGreystone
ModelCD2RMCC02XSXXX
Gas detectedCarbon dioxide (CO2)
Sensor typeDual channel non-dispersive infrared (NDIR)
Sensor accuracy+/-(30 ppm + 3% of measured value)
Measurement range0 to 2000 ppm, adjustable 1000 to 10,000 ppm
Temperature dependency+/-1.4 ppm per deg F (+/-2.5 ppm per deg C)
Response time20 seconds (T63)
Warm-up time1 minute
Sensor coverage area1,000 sq ft (100 sq m) typical
Sensor life spanOver 15 years
Transmitter accuracy+/-0.25% of span (including linearity, hysteresis, and repeatability)
Power supply24 VDC +/-20% or 24 VAC +/-10% (non-isolated half-wave rectified)
Protection circuitryReverse voltage and transient protected
Input voltage effectNegligible over specified operating range
Output signal4-20mA (3-wire), 0-5V, or 0-10V, field selectable
Current consumption4-20mA output: 75 mA @ 24 VDC, 150 mA @ 24 VAC max; voltage output: 50 mA @ 24 VDC, 100 mA @ 24 VAC max
Output drive @ 24 VDCCurrent: 550 ohm max; voltage: 10k ohm min
Ambient operating range32 to 122 deg F (0 to 50 deg C), 0 to 95% RH non-condensing
Storage temperature-40 to 158 deg F (-40 to 70 deg C)
LCDConcealed, backlit; ppm (CO2) and deg F/C (optional temp/setpoint); 0 to 10,000 ppm, 32 to 122 deg F (0 to 50 deg C); 1.4 x 0.6 in. (35 x 15 mm), 2-line x 8 character
Temp sensor100 ohm platinum RTD, IEC 751, 385 alpha, thin film; 2-wire resistive output
RelayNone
Override switchDry contact, 50 mA @ 12 VDC max, 2-wire output
SetpointNone
EnclosureWhite ABS, IP30 (NEMA 1); 3.3 x 4.7 x 1.15 in. (84 x 119 x 29 mm)
MountingSingle-gang electrical box or directly on a wall, 5 ft above the floor
Wiring connectionsScrew terminal block (14 to 22 AWG)
Self-calibrationFor spaces that drop to outdoor CO2 levels (about 400 ppm) at least 1 hour per day; for 24-hour occupancy or steady high or low CO2, turn it off and calibrate yearly
Calibration kitCDD1-CALKIT-GS (gas not included)
Calibration guarantee5 years when inside levels periodically drop to outdoor levels (Greystone terms)
Use limitsIndoor air-conditioned spaces; not for life-safety use, explosive or hazardous locations, or as a safety or emergency-stop device
ApprovalsCE
Country of originCanada