CD2OSN07R

SKU: CD2OSN07R
$787.78

Call for Availability - (510) 636-7900

Details

Details

Outside CO2 Transmitter, 0-2000 ppm, 4-20mA/0-5V/0-10V, Unheated Weatherproof Enclosure, 10k Type 3 Thermistor Temp, Relay

Needs 24 VAC/DC power. Operates only from 32 to 122 deg F; the heated model covers colder sites.

Key Features

  • Output signal: 4-20mA (3-wire), 0-5V, or 0-10V, field selectable
  • Relay: Form A (NO), 2A @ 140 VAC/30 VDC
  • Response time: about 30 minutes for a 90% step change inside the outside enclosure

Product Specifications

ManufacturerGreystone
ModelCD2OSN07R
Gas detectedCarbon dioxide (CO2)
Sensor typeDual wavelength non-dispersive infrared (NDIR)
Sensor accuracy+/-(30 ppm + 3% of measured value)
Measurement range0 to 2000 ppm, adjustable 1000 to 10,000 ppm
Altitude adjustment0 to 8,370 ft (0 to 2550 m) in 164 ft (50 m) increments
Temperature dependency+/-1.4 ppm per deg F (+/-2.5 ppm per deg C)
Response time20 seconds (T63); about 30 minutes for a 90% step change inside the outside enclosure
Warm-up time1 minute
Sensor life spanOver 15 years
Transmitter accuracy+/-0.25% of span (including linearity, hysteresis, and repeatability)
Power supply24 VDC +/-20% or 24 VAC +/-10% (non-isolated half-wave rectified)
Protection circuitryReverse voltage and transient protected
Input voltage effectNegligible over specified operating range
Output signal4-20mA (3-wire), 0-5V, or 0-10V, field selectable
Current consumptionUnheated, 4-20mA output: 75 mA max @ 24 VDC, 150 mA max @ 24 VAC; 0-5V/0-10V output: 50 mA max @ 24 VDC, 100 mA max @ 24 VAC
Operating conditions32 to 122 deg F (0 to 50 deg C), 5 to 90% RH non-condensing
Output drive @ 24 VDCCurrent: 550 ohm max; voltage: 10k ohm min
LCDConcealed, used for setting parameters; ppm (CO2), 0 to 10,000 ppm; 1.4 x 0.6 in. (35 x 15 mm), 2-line x 8 character
Temp sensor10k Type 3 NTC thermistor, +/-0.36 deg F (+/-0.2 deg C); 2-wire resistive output
RelayForm A (NO), 2A @ 140 VAC/30 VDC, 2-wire output; selectable CO2 high or CO2 low
EnclosureWeatherproof, unheated; vented, IP65 (NEMA 4X); 4.3 x 7.125 x 3.5 in. (110 x 180 x 89 mm)
MountingOutside wall, north-facing and under the eaves, out of direct sun and wind; four mounting holes
Wiring connectionsScrew terminal block (14 to 22 AWG); optional temp sensor on a 2- or 3-wire pigtail; 0.85 in. conduit knockouts
Use limitsNot for explosive or hazardous locations or as a safety or emergency-stop device
ApprovalsCE
Country of originCanada