CD2DTF59R

SKU: CD2DTF59R
$412.12

Call for Availability - (510) 636-7900

Details

Details

Duct CO2 Transmitter, 0-2000 ppm, 4-20mA/0-5V/0-10V, 10k B3435 Thermistor Temp, Relay, Cable Gland Fitting

Needs 24 VAC/DC power. Needs self-calibration turned off and a yearly calibration where the space is occupied 24 hours.

Key Features

  • Output signal: 4-20mA (3-wire), 0-5V, or 0-10V, field selectable
  • Relay: Form A (NO), 2A @ 140 VAC/30 VDC
  • UL 2043 / CSA/ULC S142: suitable for use in air handling spaces

Product Specifications

ManufacturerGreystone
ModelCD2DTF59R
Gas detectedCarbon dioxide (CO2)
Sensor typeDual channel non-dispersive infrared (NDIR)
Measurement range0 to 2000 ppm, adjustable 1000 to 10,000 ppm
Sensor accuracy+/-(30 ppm + 3% of reading)
Temperature dependency+/-1.4 ppm per deg F (+/-2.5 ppm per deg C)
Response time20 seconds (T63)
Warm-up time1 minute
Sensor life spanOver 15 years
Transmitter accuracy+/-0.25% of span (including linearity, hysteresis, and repeatability)
Input voltage effectNegligible over specified operating range
Temp sensor10k @ 77 deg F (25 deg C), +/-1%, B = 3435 +/-1% (25/85); 2-wire resistive output
Temp accuracyThermistors +/-0.36 deg F (+/-0.2 deg C) @ 77 deg F (25 deg C)
RelayForm A (NO), 2A @ 140 VAC/30 VDC, 2-wire output; programmable setpoint, hysteresis, and time delay
Operating conditions32 to 122 deg F (0 to 50 deg C), 0 to 95% RH non-condensing
Storage temperature-40 to 158 deg F (-40 to 70 deg C)
LCDBacklit; ppm (CO2), deg F/C (optional temp); 0 to 10,000 ppm, 32 to 122 deg F (0 to 50 deg C); 1.4 x 0.6 in. (35 x 15 mm), 2-line x 8 character
Wiring connectionsScrew terminal block (14 to 22 AWG)
Output drive @ 24 VDCCurrent: 550 ohm max; voltage: 10k ohm min
Power supply24 VAC +/-10% or 24 VDC +/-20%; SELV (Class 2) supply; non-isolated half-wave rectified
Current consumption4-20mA output: 75 mA @ 24 VDC, 150 mA @ 24 VAC max; voltage output: 50 mA @ 24 VDC, 100 mA @ 24 VAC max
Output signal4-20mA (3-wire), 0-5V, or 0-10V, field selectable
ProtectionClass III; reverse voltage and transient protected
UL modelMIAQDTXSC
CertificationUL 60730 and CSA E60730 (UL file E539555)
UL 2043 / CSA/ULC S142Compliant; suitable for use in air handling spaces per NEC Section 300.22(C)
Purpose of controlOperating control; Type 1 action; impulse voltage 330V; pollution degree 2
EnclosureType 4X and IP65 polycarbonate, UL94-V0 (enclosure and probe), hinged and gasketed cover; thread adapter (1/2 in. NPT to M16) and liquid-tight cable gland, cord grip 0.067 to 0.228 in. (1.7 to 5.8 mm)
DimensionsEnclosure 4.6 x 3.9 x 2.1 in. (116 x 100 x 54 mm); probe 6.0 in. long x 0.88 in. diameter (152 x 22.5 mm)
MountingOutside of a return air duct with the sampling probe inserted; straight duct at least 5 ft from corners
Self-calibrationFor spaces that drop to outdoor CO2 levels (about 400 ppm) at least 1 hour per day; for 24-hour occupancy or steady high or low CO2, turn it off and calibrate yearly
Calibration kitCDD1-CALKIT-GS (gas not included)
Calibration guarantee5 years when inside levels periodically drop to outdoor levels (Greystone terms)
Use limitsIndoor air-conditioned spaces; not for life-safety use, explosive or hazardous locations, or as a safety or emergency-stop device
EU conformityCE
Country of originCanada