B278+AFRB24

SKU: B278AFRB24
$1,202.85

Call for Availability - (510) 636-7900

Details

Details

B278+AFRB24 3 in. 2-Way CCV with Spring Return Actuator, 24 VAC/DC, On/Off

Equal percentage ball valve for chilled or hot water, up to 60% glycol, with on/off control. Fail position (open or closed) is set at the factory; state it when ordering.

Key Features

  • Cv: 130
  • Close-off: 100 psi
  • Control: on/off
  • Running time: 75 s

Product Specifications

ManufacturerBelimo
ModelB278AFRB24 (B278+AFRB24)
ValveB278
Valve size3" (80)
Fluidchilled or hot water, up to 60% glycol
Fluid Temp Range (water)0 to 212 deg F (-18 to 100 deg C)
Body Pressure Rating400 psi
Close-off pressure100 psi
Flow characteristicequal percentage
Pipe connection typeInternal thread NPT (female)
Servicingmaintenance-free
Flow Pattern2-way
Leakage rate0% for A – AB
Controllable flow range75 deg
Cv130
Valve bodyNickel-plated brass body
Stemstainless steel
Stem sealEPDM (lubricated)
SeatPTFE
Characterized discTEFZEL
O-ringEPDM (lubricated)
Ballstainless steel
Suitable actuators, non-spring returnARB(X)
Suitable actuators, spring returnAFRB(X)

Actuator: AFRB24

Nominal voltageAC/DC 24 V
Nominal voltage frequency50/60 Hz
Nominal voltage rangeAC 19.2 to 28.8 V / DC 21.6 to 28.8 V
Power consumption in operation5.5 W
Power consumption in rest position1.5 W
Transformer sizing7.5 VA
Overload Protectionelectronic throughout 0 to 95 deg rotation
Direction of motion motorselectable by ccw/cw mounting
Direction of motion fail-safereversible with cw/ccw mounting
Manual override5 mm hex crank (3/16" Allen), supplied
Angle of rotation90 deg
Running time (motor)75 s / 90 deg
Running time fail-safe<20 s
Sound power level motor45 dB(A)
Sound power level, fail-safe62 dB(A)
Position indicationMechanical
Power source ULClass 2 Supply
Degree of protection NEMA/ULNEMA 2
HousingUL Enclosure Type 2
Agency ListingcULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02 CE acc. to 2014/30/EU and 2014/35/EU
Quality StandardISO 9001
UL 2043 CompliantSuitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC
Ambient humidityMax. 95% RH, non-condensing
Ambient temperature-22 to 122 deg F (-30 to 50 deg C)
Storage temperature-40 to 176 deg F (-40 to 80 deg C)
Servicingmaintenance-free
Weight5.3 lb (2.4 kg)
Housing materialGalvanized steel and plastic housing
Innovative motorizationThe actuator uses the powerful Belimo M600 microchip in combination with the INFORM method. It provides the full starting torque from a standstill with high precision (sensorless INFORM-Drive by Prof. Schrödl).