B216+TR24-SR-T US

SKU: B216TR24SRTUS
$319.05

Call for Availability - (510) 636-7900

Details

Details

B216+TR24-SR-T US 1/2 in. 2-Way CCV with Non-Spring Return Actuator, 24 VAC/DC, 2-10V

Equal percentage ball valve for chilled or hot water, up to 60% glycol, with modulating 2-10 VDC control. Holds position on power loss.

Key Features

  • Cv: 16
  • Close-off: 200 psi
  • Control: 2-10 VDC
  • Running time: 90 s

Product Specifications

ManufacturerBelimo
ModelB216TR24SRTUS (B216+TR24-SR-T US)
ValveB216
Valve size0.5" (15)
Fluidchilled or hot water, up to 60% glycol
Fluid Temp Range (water)0 to 250 deg F (-18 to 120 deg C)
Body Pressure Rating600 psi
Close-off pressure200 psi
Flow characteristicequal percentage
Leakage rate0% for A–AB
Pipe connectionInternal thread NPT (female)
Servicingmaintenance-free
Flow Pattern2-way
Controllable flow range75 deg
Cv16
No Characterized DiscTRUE
Valve bodyNickel-plated brass body
Stemstainless steel
Stem sealEPDM (lubricated)
SeatPTFE
Characterized discTEFZEL
O-ringEPDM (lubricated)
Ballstainless steel
Suitable actuators, non-spring returnTR LRB(X) LRQB(X) NRB(X) N4
Suitable actuators, spring returnTFRB(X) LF

Actuator: TR24-SR-T US

Nominal voltageAC/DC 24 V
Nominal voltage frequency50/60 Hz
Nominal voltage rangeAC 19.2 to 28.8 V / DC 21.6 to 28.8 V
Power consumption in operation0.5 W
Transformer sizing1 VA
Overload Protectionelectronic throughout full rotation
Operating range Y2 to 10 V
Operating range Y note4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor)
Input impedance100 kΩ for 2 to 10 V (0.1 mA), 500 Ω for 4 to 20 mA
Direction of motion motorselectable with switch
Manual overridepush down handle
Angle of rotation90 deg
Running time (motor)90 s / 90 deg
Sound power level motor35 dB(A)
Position indicationintegrated into handle
Power source ULClass 2 Supply
Degree of protection IEC/ENIP40
Degree of protection NEMA/ULNEMA 1
HousingUL Enclosure Type 1
Agency ListingcULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02 CE acc. to 2014/30/EU and 2014/35/EU
Quality StandardISO 9001
UL 2043 CompliantSuitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC
Ambient humidityMax. 95% RH, non-condensing
Ambient temperature-22 to 122 deg F (-30 to 50 deg C)
Storage temperature-40 to 176 deg F (-40 to 80 deg C)
Servicingmaintenance-free
Weight0.85 lb (0.39 kg)
AC/DC 24 V, modulatingOverride control (frost protection circuit)