B214+TFRB24-3 1/2 in. 2-Way CCV with Spring Return Actuator, 24 VAC/DC, Floating

Equal percentage ball valve for chilled or hot water, up to 60% glycol, with on/off or floating control. Fail position (open or closed) is set at the factory; state it when ordering.

Key Features

  • Cv: 7.4
  • Close-off: 200 psi
  • Control: on/off or floating
  • Running time: 95 s

Product Specifications

ManufacturerBelimo
ModelB214TFRB243 (B214+TFRB24-3)
ValveB214
Valve size0.5" (15)
Fluidchilled or hot water, up to 60% glycol
Fluid Temp Range (water)0 to 250 deg F (-18 to 120 deg C)
Body Pressure Rating600 psi
Close-off pressure200 psi
Flow characteristicequal percentage
Leakage rate0% for A–AB
Pipe connectionInternal thread NPT (female)
Servicingmaintenance-free
Flow Pattern2-way
Controllable flow range75 deg
Cv7.4
Valve bodyNickel-plated brass body
Stemstainless steel
Stem sealEPDM (lubricated)
SeatPTFE
Characterized discTEFZEL
O-ringEPDM (lubricated)
Ballstainless steel
Suitable actuators, non-spring returnTR LRB(X) LRQB(X) NRB(X) N4
Suitable actuators, spring returnTFRB(X) LF

Actuator: TFRB24-3

Nominal voltageAC/DC 24 V
Nominal voltage frequency50/60 Hz
Nominal voltage rangeAC 19.2 to 28.8 V / DC 21.6 to 28.8 V
Power consumption in operation2.5 W
Power consumption in rest position1W
Transformer sizing4 VA
Overload Protectionelectronic throughout 0 to 95 deg rotation
Position feedback U noteNo Feedback
Direction of motion motorselectable with switch 0/1
Direction of motion fail-safereversible with cw/ccw mounting
Angle of rotationMax. 95 deg
Running time (motor)95 s
Running time fail-safe<25 s @ 68 deg F (20 deg C)
Sound power level motor35 dB(A)
Sound power level, fail-safe62 dB(A)
Position indicationMechanical
Power source ULClass 2 Supply
Degree of protection NEMA/ULNEMA 2
HousingUL Enclosure Type 2
Agency ListingcULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU
Quality StandardISO 9001
UL 2043 CompliantSuitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC
Ambient humidityMax. 95% RH, non-condensing
Ambient temperature-22 to 122 deg F (-30 to 50 deg C)
Storage temperature-40 to 176 deg F (-40 to 80 deg C)
Servicingmaintenance-free
Weight1.3 lb (0.59 kg)
Housing materialUL94-5VA