B212+LF24-SR US

SKU: B212LF24SRUS
$464.85

Call for Availability - (510) 636-7900

Details

Details

B212+LF24-SR US 1/2 in. 2-Way CCV with Spring Return Actuator, 24 VAC/DC, 2-10V

Equal percentage ball valve for chilled or hot water, up to 60% glycol, with modulating 2-10 VDC control. Fail position (open or closed) is set at the factory; state it when ordering. No manual override.

Key Features

  • Cv: 3
  • Close-off: 200 psi
  • Control: 2-10 VDC, 2-10 VDC feedback
  • Torque: 35 lb-in

Product Specifications

ManufacturerBelimo
ModelB212LF24SRUS (B212+LF24-SR US)
ValveB212
Valve size0.5" (15)
Fluidchilled or hot water, up to 60% glycol
Fluid Temp Range (water)0 to 250 deg F (-18 to 120 deg C)
Body Pressure Rating600 psi
Close-off pressure200 psi
Flow characteristicequal percentage
Leakage rate0% for A–AB
Pipe connectionInternal thread NPT (female)
Servicingmaintenance-free
Flow Pattern2-way
Controllable flow range75 deg
Cv3
Valve bodyNickel-plated brass body
Stemstainless steel
Stem sealEPDM (lubricated)
SeatPTFE
Characterized discTEFZEL
O-ringEPDM (lubricated)
Ballstainless steel
Suitable actuators, non-spring returnTR LRB(X) LRQB(X) NRB(X) N4
Suitable actuators, spring returnTFRB(X) LF

Actuator: LF24-SR US

Nominal voltageAC/DC 24 V
Nominal voltage frequency50/60 Hz
Nominal voltage rangeAC 19.2 to 28.8 V / DC 21.6 to 35.0 V
Power consumption in operation2W
Power consumption in rest position0.8 W
Transformer sizing3.5 VA
Connection supply/controlcable 3 ft. (1 m), 4x 0.75 mm2
Parallel operationYes (note the performance data)
Communicative controlMP-Bus
Number of nodesMP-Bus max. 16
Torque35 lb-in (4 Nm)
Torque Fail-Safe4 Nm
Operating range Y2 to 10 V
Input impedance100 kΩ
Operating range Y variableStart point 0.5 to 30 V End point 2.5 to 32 V
Operating modes optionalvariable (VDC, on/off, floating point)
Position feedback U2 to 10 V
Position feedback U noteMax. 1 mA
Position feedback U variableStart point 0.5 to 8 V End point 2.5 to 10 V
Position accuracy+/-5%
Direction of motion motorselectable with switch L/R
Direction of motion variableelectronically reversible
Direction of motion fail-safeselectable by mounting L/R
Manual overrideNo
Angle of rotationMax. 95 deg
Angle of rotation noteAdjustable 37 to 100% with integrated mechanical limitation
Running time (motor)150 s / 90 deg
Running time motor variable75 to 300 s
Running time fail-safe<20 s @ -20 to 50 deg C, <60 s @ -30 deg C
Sound power level, motor36 dB(A)
Adaptation Setting Rangewith Belimo Assistant 2
Override controlMIN (minimum position) = 0% MID (intermediate position, AC only) = 50% MAX (maximum position) = 100%
Override control variableMIN = 0%...(MAX – 32%) MID = MIN...MAX MAX = (MIN + 32%)...100%
Mechanical interfaceUniversal shaft clamp 8 to 16 mm
Position indicationMechanical
Service lifeMin. 60'000 fail-safe positions
Power source ULClass 2 Supply
Degree of protection NEMA/ULNEMA 2
HousingUL Enclosure Type 2
Agency ListingcULus acc. To UL 873 and CAN/CSA C22.2 No. 24-93
Quality StandardISO 9001
UL 2043 CompliantSuitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC
Ambient humidityMax. 95% RH, non-condensing
Ambient temperature-22 to 122 deg F (-30 to 50 deg C)
Storage temperature-40 to 176 deg F (-40 to 80 deg C)
Servicingmaintenance-free
Weight3.2 lb (1.5 kg)

Product Resources