AQ2W-BA2AABX
Details
Details
Senva AQ2W-BA2AABX Wall RH/Temp Sensor, BACnet/Modbus, No Display
Mounts on the wall surface over a junction box; a concealing ring covers oversized cutouts.
Communicates over BACnet MS/TP or Modbus RTU on 3-wire RS-485 (switch selectable).
Includes a solid-state relay (1A at 30 VAC/DC, NO or NC selectable) that can trip on an RH or temp setpoint, or air quality.
Needs 16-30 VDC or 24 VAC; one side of the transformer secondary is tied to signal common, so a dedicated transformer is recommended.
Product Specifications
| Manufacturer | Senva |
|---|---|
| Model | AQ2W-BA2AABX |
| Mounting | Surface wall |
| Output type | BACnet/Modbus (RS-485) |
| CO2 | None |
| Relative humidity | 2% RH sensor |
| TVOC | None |
| Advanced sensors | None |
| Temperature | Transmitter |
| Display | None |
| Setpoint slider | None |
| Slider offset resistor | None |
| Pushbutton | None |
| PIR sensor | None |
| Power supply | 16-30 VDC/24 VAC, 3.5W nominal, 4W max (non-display) |
| Power wiring | One side of transformer secondary is connected to signal common; dedicated transformer recommended |
| Protocol | BACnet MS/TP or Modbus RTU |
| Connection | 3-wire RS-485 with isolated ground |
| Data rate | 9600, 19200, 38400, 57600, 76800, 115200 (switch selectable) |
| Address range | 0-127 |
| Relay | Solid-state, 1A @ 30 VAC/DC |
| Relay polarity | NO/NC (selectable) |
| Relay source | RH setpoint, temp setpoint, air quality, off (selectable) |
| RH sensor type | Digital CMOS |
| RH accuracy | +/-2% over 0 to 80% RH |
| RH resolution | 0.05% RH |
| RH response time | 30 s (63% of reading at 77 deg F (25 deg C), 197 fpm (1 m/s) airflow) |
| RH sample rate | 3 s |
| RH operating range | 0 to 100% RH (non-condensing) |
| RH operating conditions | -4 to 140 deg F (-20 to 60 deg C) @ RH>90%; -4 to 176 deg F @ 50% RH |
| Temperature sensor type | Silicon band-gap |
| Temperature nominal accuracy | +/-0.54 deg F (0.3 deg C) (operating range) |
| Temperature maximum accuracy | +/-0.9 deg F (0.5 deg C) (at 77 deg F (25 deg C)), +/-1.8 deg F (1.0 deg C) |
| Temperature resolution | 0.18 deg F (0.1 deg C) |
| Temperature response time | 30 s |
| Temperature sample rate | 3 s |
| Operating temperature | 32 to 122 deg F (0 to 50 deg C) |
| Operating humidity | 0-95% non-condensing |
| Enclosure material | ABS plastic |
| Dimensions | 5.67 in. H x 3.00 in. W x 1.07 in. D (with concealing ring: 6.35 in. H x 3.69 in. W x 1.25 in. D) |
| Accreditation | RESET Air accredited monitor |
| Field-replaceable sensors | RH and temp |
| Warranty | 7 years limited; 3 years on CO2 sensor; 2 years on all other sensors |
| Compliance | CE, RoHS |