298-03109 1/2 in. NPT 2-Way Normally Open Globe Valve with OpenAir GCA161.1U Spring Return Actuator on Rack and Pinion Linkage, 0-10V, 24 VAC/DC

Springs back to open on power loss.

Ships with the actuator preloaded at the factory.

Normal-duty packing limits media to 20 to 250 deg F.

Limits modulating differential to 50 psi.

Needs the ASZ6.6 stem heater for media below 32 deg F.

Key Features

  • Cv: 1.6
  • Close-off: 250 psi
  • Flow characteristic: equal percentage
  • Trim: stainless steel
  • Stroke: 3/4 in.
  • Feedback: 0 to 10 VDC

Product Specifications

ManufacturerSiemens
Model29803109 (298-03109)
ProductFlowrite 599 Series 2-way globe valve and actuator assembly
Valve body part number599-03109
ActuatorOpenAir GCA161.1U Spring Return Actuator on Rack and Pinion Linkage, 0-10V, 24 VAC/DC
Fail actionSpring return to the valve normal position on power failure; this NO valve fails open
Line size1/2 in (15 mm)
Cv (Kvs)1.6 (1.37)
ActionNormally open (NO)
Flow characteristicEqual percentage
TrimStainless steel
PackingNormal duty (EPDM O-rings)
End connectionsIT x IT (internal thread NPT x internal thread NPT)
Medium temperature20 deg F to 250 deg F (-7 deg C to 120 deg C)
Controlled mediumSaturated steam, water, 50% water-glycol solutions
Maximum recommended differential pressure, modulating, liquid50 psi (345 kPa)
Maximum recommended differential pressure, modulating, steam50 psi (345 kPa)
Maximum inlet pressureWater: per pressure-temperature rating; steam: 100 psig (690 kPa)
Water capacity (gpm at pressure drop)1 psi: 1.6; 5 psi: 3.6; 10 psi: 5.1; 25 psi: 8.0; 50 psi: 11.3
Body materialUNS CA 844 bronze
Valve body ratingANSI Class 250
Pressure-temperature rating (bronze, ANSI Class 250)-20 to +150 deg F (-30 to 66 deg C): 400 psig (2758 kPa); +200 deg F (93 deg C): 385 psig (2655 kPa); +250 deg F (121 deg C): 365 psig (2586 kPa); +300 deg F (149 deg C): 335 psig (2300 kPa); +350 deg F (177 deg C): 300 psig (2068 kPa)
StemStainless steel ASTM A582 Type 303
Seat styleSingle seat, metal-to-metal
Stem travel (stroke)3/4 in (20 mm)
BonnetDirect-coupled universal bonnet
Controlled medium (series)Saturated steam, water, 50% water-glycol solutions
Rangeability>100:1
Leakage rateANSI Leakage Class IV (0.01% of Cv)
Mounting locationNEMA 1 (interior only)
Canadian Registration Number0C24303.5
Installation orientationBest with actuator above the valve body; any position between vertical and horizontal; not recommended with the actuator below horizontal or upside down
Parts materialsGasket copper; NO 3/4 to 2 in bonnet brass; stem and plug assembly bronze or stainless steel; valve body bronze; O-ring EPDM; NC cap brass
Stem heater (accessory)ASZ6.6 stem heating element required for media below 32 deg F (0 deg C); 24 VAC/DC +/-20%, 40 VA/30 W max
Valve dimension A1-7/16 (36) in
Valve dimension B2-15/16 (74) in
Valve dimension C1-1/4 (31) in
Valve weight3 lb (1.4 kg)
Close-off pressure, this assembly250 psi (1724 kPa)
Close-off rating basisAccording to ANSI/FCI 70-2; ANSI Class IV (0.01% of Cv)
Valve actuator assembly599-03609 = rack and pinion linkage + OpenAir GCA161.1U electronic actuator, for modulating control; actuator prefix code 298 (298-XXXXX = linkage, actuator and valve assembly); linkage alone = 599-03610
Actuator typeElectro-mechanical, spring return, 'Electro-Mechanical - 24 VAC' in valve selection tables; brushless DC motor with stall protection
Actuator operating voltage24 VAC +/-20% or 24 VDC +/-10% (G-G0)
Actuator frequency50/60 Hz
Actuator power consumptionRunning 7 VA / 5 W; holding 5 VA / 3 W
Power consumption for transformer sizing (valve assembly)9 VA; max 9 actuators per Class 2 supply circuit (80% of transformer VA)
Actuator equipment ratingClass 2, in accordance with UL/CSA
Control signal (Y-G0)0 to 10 VDC (max. 35 VDC)
Input resistance>100K ohms
Position feedback (U-G0)0 to 10 VDC position output; maximum output current +/-1 mA
Actuator operationAngle of rotation proportional to the 0 to 10 VDC signal on wire Y; 0 to 10 VDC feedback between U and G0 monitors position
Built-in optionsStandard cable; position feedback; no dual auxiliary switches, no signal inversion, no offset/span adjustment on this model
Actuator torque160 lb-in (18 Nm) running and spring return (operating with 24 VAC); maximum <360 lb-in (40 Nm); at -25 deg F spring return is 142 lb-in (16 Nm)
Running time (90 deg)90 s operating with motor
Spring return time15 s typical closing on power loss (submittal: 15 s typical, 30 s max)
Actuator fail actionSpring return; on power failure or when operating voltage is shut off all models return to the 0 position (bi-directional fail-safe spring return)
Direct / reverse acting (valve assembly)Direct-acting or reverse-acting control is set by the actuator's mounting orientation on the linkage (single end-stop tab upper left = direct, upper right = reverse); in both cases the actuator is engaged with the valve stem full up (min 1.80 in (46 mm) between bottom of linkage stem coupling and top of bonnet)
Factory preloadActuators are preloaded at the factory (TI: 5 deg preload as shipped); if preload is lost it must be reset per the preload procedure
Angle of rotation90 deg nominal, 95 deg maximum
Actuator manual overrideHex key in override opening, turned in arrow direction; gear train lock pin holds position (turn only about 5 deg); release by restoring power and control signal, or with power absent turn key in arrow direction and remove
Overload protectionOverload protected over the full range to prevent damage if blocked
Actuator enclosureNEMA 2, IP54 per EN 60 529, mounted vertical to horizontal 90 deg; NEMA 3R with weather shield accessory in vertical position (damper-actuator accessory; fit on the valve linkage not stated)
Mounting positions (valve assembly)Acceptable NEMA 2 mounting positions: upright through 90 deg to either side (figure)
Ambient operating temperature-25 deg F to 130 deg F (-32 deg C to 55 deg C)
Storage and transport temperature-40 deg F to 158 deg F (-40 deg C to 70 deg C)
Ambient humidity95% rh non-condensing
Actuator approvalsUL listed to UL60730 (to replace UL873); cUL certified to C22.2 No. 24-93; CE: EMC 2004/108/EC, immunity EN61000-6-2, emissions EN61000-6-3
Electrical connectionPre-cabled, 18 AWG, 3 ft (0.9 m) standard cable
Wiring1 red = G supply (SP); 2 black = G0 neutral (SN); 8 gray = Y 0 to 10 VDC input; 9 pink = U 0 to 10 VDC position feedback
Power supply wiringEarth-ground isolating step-down Class 2 transformers; do not use autotransformers; max Class 2 transformer 100 VA; wiring per NEC and local codes
Actuator housing materialDie-cast aluminum alloy; silicone-free gear lubrication
Noise level<45 dBA (running)
Life cycleDesigned for over 60,000 full strokes and a minimum of 1.5 million repositions at rated torque and temperature
Weight (actuator alone)4.85 lb (2.2 kg); linkage and assembly weight not printed
Dimensions (actuator alone)11-13/16 in (300 mm) H x 4-3/4 in (120 mm) W x 2-7/8 in (72 mm) D
Dimensions (linkage + actuator on valve)14-1/2 in (368 mm) max height; 13 in (330 mm) max; 5 in (127 mm) wide; 5-1/8 in (131 mm) deep; 1-1/2 in (38 mm); 2-1/2 in (64 mm)
Service clearances (valve assembly)Min 10 in (254 mm) from top; min 4 in (102 mm) each side; min 12 in (305 mm) from front; min 8 in (203 mm) from back