261-02017 1/2 in. Powermite MT NPT 2-Way Normally Closed Globe Valve with SSC161.05U Electromotoric Non-Spring Return Actuator, 0-10V, 24 VAC/DC

Holds its last position on power loss.

Runs on 24 VAC or 24 VDC.

Self-calibrates its stroke at every power-up.

Takes a 0-10V control signal only; no 4-20 mA input.

Mounts upright or tilted, above horizontal only.

Handles water, glycol solutions up to 50% or low-pressure steam under 15 psi, at 35 to 250 deg F.

Limits modulating differential to 50 psi for liquids and 15 psi for steam.

Key Features

  • Cv: 0.63
  • Close-off: 95 psi
  • Flow characteristic: modified equal percentage
  • Trim: stainless steel
  • Stroke: 7/32 in.
  • Feedback: 0 to 10 VDC

Product Specifications

ManufacturerSiemens
Model26102017 (261-02017)
ProductPowermite MT Series 2-way globe valve and actuator assembly
Valve body part number599-02017
ActuatorSSC161.05U Electromotoric Non-Spring Return Actuator, 0-10V, 24 VAC/DC
Fail actionNon-spring return; holds last position on power failure
Valve seriesPowermite MT Series terminal unit valve
Line size1/2 in (15 mm)
Cv (Kvs)0.63 (0.54)
ActionNormally closed (NC)
Flow characteristicModified equal percentage
TrimStainless steel
Body materialC37700 forged brass
PackingEPDM O-rings
End connectionsinternal thread NPT x internal thread NPT
Stem travel (stroke)7/32 in (5.5 mm)
Valve spring range (pneumatic use)10 to 15 psi (69 to 102 kPa)
Controlled mediumWater, low pressure steam (<15 psi), water-glycol solutions to 50%
Medium temperature35 deg F to 250 deg F (2 deg C to 120 deg C)
Maximum recommended differential pressure, modulating, liquid50 psi (345 kPa)
Maximum recommended differential pressure, modulating, steam15 psi (103 kPa)
Pressure-temperature rating (ANSI Class 250)-20 to 150 deg F (-30 to 66 deg C): 400 psig (2758 kPa); 200 deg F (93 deg C): 385 psig (2655 kPa); 250 deg F (121 deg C): 365 psig (2586 kPa); 300 deg F (149 deg C): 335 psig (2300 kPa); 350 deg F (177 deg C): 300 psig (2068 kPa)
Body styleGlobe
Valve body ratingANSI Class 250
StemStainless steel ASTM A582 Type 303
Seat styleMetal-to-metal
BonnetDirect coupled universal bonnet
RangeabilityCv <1: >50:1; Cv >1: >100:1
Close-off ratings basisAccording to ANSI/FCI 70-2
Leakage rateANSI Leakage Class IV (0.01% of Cv)
Mounting locationNEMA 1 (interior only)
InstallationFlow follows the direction of the arrow on the valve body; best performance with actuator above the valve body; any position between vertical and horizontal; not recommended below horizontal or upside down; allow service space per actuator service envelope
ServiceReplace the valve if inoperable
Canadian Registration Number0C24303.5
Valve dimension A (body centerline to NPT port end)1-3/8 in (35 mm)
Valve dimension B (body bottom to body top)2-1/4 in (57 mm)
Valve dimension C (pipe centerline to body top)1-5/16 in (33 mm)
Valve weight0.96 lb (0.44 kg)
Close-off pressure, this assembly95 psi (655 kPa)
Actuator typeElectromotoric actuator for Powermite MT Series 2-way and 3-way globe valves
Actuator operating voltageAC 24 V (+/-15%) or DC 24 V (+/-20%)
Actuator power consumptionNormal operation 3.5 VA (AC); 1.5 W (DC). Peak (ultra cap recharge): N/A
Control signalModulating DC 0...10 V to Y; valve opens/closes in proportion; at DC 0 V stem retracted, NC valve fully closed, NO valve fully open; actuator characteristic linear
Position feedbackDC 0...10 V proportional to stroke of the actuator stem; max output current 1 mA; max output voltage '-'; resolution 1:100
Actuator running time27.5 s +/-25% for 5.5 mm (5 s/mm +/-25%)
Actuator fail actionFail-in-place / NSR: 'When no power is supplied, the SSC161.05U actuator maintains its current position'
Spring return / fail-safe timeNot applicable (no fail-safe)
Actuator weight9.7 ounces (276 g)
Input impedance100 kOhm
Self-calibrationOn power-up: fully retracted -> fully extended -> setpoint; 'Never intervene manually during self-calibration'; correct calibration only with valve stroke > 0.05 in (1.2 mm); retries after 10 s; 'After three failed calibration attempts, the actuator stem remains in the extended position and the valves are open'
Actuator manual override3 mm Allen wrench; open cover, press and hold button (a) at least 3 s (actuator then ignores the control signal), turn wrench clockwise = stem down, counter-clockwise = stem up; position retained; press button 3 s again to exit, actuator self-calibrates; without power no button press needed
Wiring terminalsG system potential (AC/DC 24 V); G0 system neutral; Y control signal DC 0...10 V; U feedback signal; M measurement reference
Parallel operationMax. 10 modulating actuators, provided the controller output is sufficient
Positioning force67 lb (300 N)
Actuator stroke0.05 to 0.25 in (1.2...6.5 mm); valve stroke 7/32 in (5.5 mm)
Actuator frequency50/60 Hz
Primary fuse or breakerExternal, 2 A quick blow (2AF in connection diagrams)
Actuator enclosureHousing protection degree NEMA 2 / IP20 (EN 60529); protection class III (EN 60730); pollution degree 2; overvoltage category I
Actuator ambient temperatureOperation 34 to 122 deg F (1...50 deg C); transport and storage -13 to 158 deg F (-25...70 deg C)
Ambient humidity / altitudeOperation 5...95% r.h. non condensing; transport <95% r.h. non condensing; storage 5...95% r.h. non condensing; min. 700 hPa (max. 3,000 m above sea level) in operation
Actuator media temperaturePermissible temperature of medium in the connected valve 34 to 248 deg F (1...120 deg C); MT valve bodies rated 35 to 250 deg F (2 to 120 deg C)
Actuator approvalsUL per UL60730-1, UL60730-2-14; cUL per CSA-CAN E60730-1, E730-2-14; FCC CFR 47 Part 15 Class B; ICES-003 CAN ICES-3 (B)/NMB-3(B); CE; RCM; UKCA
Electrical connection / wire sizePermissible length for signal lines 65 ft (20 m); wire cross section 18...20 AWG (0.5...0.75 mm2); cable diameter <0.22 in (5.5 mm); wired to a removable terminal block under the cover
Actuator housingCover/base PC + ABS, color 2003 Ti-Gray; connecting nut brass
Mounting / connection to valveDirect mounting with brass 3/4 in coupling nut, hand-tightened, no tools; 'Do not use pipe wrenches, pliers or similar tools'; 'Avoid lateral pressure or (cable) tension on the mounted actuator'
Actuator mounting positionOrientation: above horizontal
Stem direction vs valveStem extends: NO valve closes, NC valve opens; stem retracts: NO valve opens, NC valve closes