22UTH-550X Outdoor Humidity and Temperature Sensor, Modbus RTU, Radiation Shield
Two 0-5V/0-10V outputs (temp and humidity) in addition to Modbus; ranges set over the network.
Shield keeps rain and radiated heat from roofs and nearby surfaces off the sensing elements.
Key Features
- Nominal voltage: 24 VAC/DC
- Operating condition airflow: max. 40 ft/s (12 m/s)
Product Specifications
| Manufacturer | Belimo |
|---|---|
| Model | 22UTH550X (22UTH-550X) |
| Communication | Modbus RTU |
| Output signal active temperature | 0 to 5 V, 0 to 10 V |
| Output signal active humidity | 0 to 5 V, 0 to 10 V |
| Nominal voltage | 24 VAC/DC |
| Nominal voltage range | 19 to 29 VAC / 15 to 35 VDC |
| Power consumption AC | 4.3 VA |
| Power consumption DC | 2.3 W |
| Electrical connection | Pluggable spring-loaded terminal block max. 2.5 mm2 |
| Cable entry | Cable gland with strain relief 2x dia. 6 mm (1/2 in. NPT conduit adapter included) |
| Application | Air |
| Voltage output | 2 x 0 to 5 V, 0 to 10 V, min. resistance 10k |
| Output signal active note | output 0 to 5/10 V with jumper adjustable |
| Measured values | relative humidity; Absolute humidity; Dew point; Enthalpies; Temperature |
| Measuring range temperature | Adjustable via Modbus -5 to 175 deg F (-20 to 80 deg C) (default setting) |
| Accuracy temperature | +/-0.5 deg F @ 77 deg F (+/-0.3 deg C @ 25 deg C) |
| Long-term stability temperature | +/-0.09 deg F p.a. @ 70 deg F (+/-0.05 deg C p.a. @ 21 deg C) |
| Time constant temperature (63%) in the room | Typical 351 s @ 0 m/s |
| Sensing element technology humidity | Polymer-based capacitive sensor with stainless steel wire mesh filter |
| Measuring range humidity | adjustable via Modbus; Default setting: 0 to 100% RH |
| Measuring range absolute humidity | adjustable via Modbus default setting: 0 to 80 g/m3 |
| Measuring range enthalpy | adjustable via Modbus default setting: 0 to 85 kJ/kg |
| Measuring range dew point | adjustable via Modbus default setting: -5 to 175 deg F (-20 to 80 deg C) |
| Accuracy humidity | +/-2% between 0 to 80% RH @ 77 deg F (25 deg C) |
| Long term stability humidity | +/-0.3% RH p.a. @ 70 deg F (21 deg C) @ 50% RH |
| Time constant humidity (63%) in the room | Typical 16 s @ 0 m/s |
| Protection class IEC/EN | III, Safety Extra-Low Voltage (SELV) |
| Power source UL | Class 2 Supply |
| Degree of protection IEC/EN | IP65 |
| Degree of protection NEMA/UL | NEMA 4X |
| Enclosure | UL Enclosure Type 4X |
| EU Conformity | CE Marking |
| Certification IEC/EN | IEC/EN 60730-1 |
| Quality Standard | ISO 9001 |
| UL 2043 Compliant | Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC |
| Type of action | Type 1 |
| Rated impulse voltage supply | 0.8 kV |
| Pollution degree | 3 |
| Ambient humidity | short-term condensation permitted |
| Ambient temperature | -30 to 120 deg F (-35 to 50 deg C) |
| Fluid humidity | short-term condensation permitted |
| Fluid temperature | -30 to 122 deg F (-35 to 50 deg C) |
| Operating condition airflow | max. 40 ft/s (12 m/s) |
| Housing | Cover: PC, orange; Bottom: PC, orange; Seal: NBR70, black; UV resistant; UL94 5VA |
| Cable gland | PA6, black |
| Weather protection | Weather and radiated heat shield (radiation shield) |
| Parts included | Cable gland dia. 6 to 8 mm, dowels, screws, 1/2 in. NPT conduit adapter |