FC 102 VFD Bypass Panel, 1 HP, 3-Phase 600 VAC, NEMA 12, 3-Contactor Bypass, Fused Main Disconnect

One enclosure holds the drive, EMB2 electromechanical bypass, main disconnect switch, and main and drive fuses.

Needs 3-phase input power.

A drive input contactor isolates the drive from the line, and a Test position runs the motor in bypass while the drive stays powered.

In bypass the motor runs across the line at full speed, protected by a Class 20 overload relay set to the motor full-load amps.

EMB2 adds automatic transfer to bypass on a drive fault, run permissive, and basic fire mode in bypass.

Key Features

  • Bypass: 3-contactor, EMB2 electromechanical
  • Drive output current: 2.6 A at 525-550 VAC, 2.4 A at 525-600 VAC (continuous)
  • Fuses: main and drive fuses
  • RFI filter: none

Product Specifications

ManufacturerDanfoss
Model178U9450
ProductVLT HVAC Drive FC 102 panel assembly (traditional bypass)
Panel model codeS102001T6E123CMM2XXSXXZXXGXXXXXXXXXXXXXX
Drive type codeFC-102P1K1T6E55HXXGX7SXSXXXXAXBXCXXXXDX
Motor rating1 HP
Drive output current, continuous (525-550 VAC)2.6 A
Drive output current, continuous (525-600 VAC)2.4 A
Drive output current, intermittent (525-550 VAC)2.9 A
Drive output current, intermittent (525-600 VAC)2.6 A
Supply voltage3-phase 600 VAC
EnclosureNEMA 12
Bypass3-contactor bypass
Bypass controlEMB2 electromechanical bypass (Drive/Off/Bypass/Test selector, bypass pilot light)
Bypass featuresSafety interlock, common start/stop, automatic bypass, run permissive in bypass, basic fire mode
Bypass overloadClass 20 overload relay, set to motor FLA
DisconnectMain disconnect switch
FusingMain and drive fuses
Control power24 VDC switch-mode power supply
Line reactor / filterNone (DC link reactor built into the drive)
RFI filterNone
Brake chopperNone
KeypadGraphical
Conformal coatingNone
Communication cardsNone (BACnet MS/TP, Modbus RTU, Metasys N2, and Apogee FLN built into the drive)
I/O cardsNone
MotorsSingle motor
Drive frame sizeA5
Max ambient temperature40 deg C / 104 deg F
Humidity95% non-condensing
Fuses F15A, B, C600 VAC, 3 A, Class J
Fuses F16A, B, CBussmann LP-CC-5
Fuses F900,F901,F902Bussmann FWH-020A6F 20A
Terminals L1, L2, L3/ GND55 (6.21) / 25 (2.8) in-lb (N-m); 75 deg C Copper conductors
Terminals T1, T2, T3/ GND20 (2.3) / 25 (2.8) in-lb (N-m); 75 deg C Copper conductors
Terminals TB17 (0.8) in-lb (N-m); Copper conductors
Seismic certificationOSHPD pre-approval OSP-0087; anchorage: rigid wall mount; SDS 1.58, z/h 1.0, ip 1.5
Electrical drawing007N0630
Mechanical drawing176U5290
Net weight66.7 lb