178U9249

SKU: 178U9249
$4,396.08
Request a Freight Quote

Ships by truck freight. Our sales team replies with delivered pricing, usually within one business day.

Details

Details

FC 102 VFD Bypass Panel, 7.5 HP, 3-Phase 460 VAC, NEMA 3R, 2-Contactor Bypass, Main Circuit Breaker

One enclosure holds the drive, EMB2 electromechanical bypass, main breaker, and drive fuses.

Needs 3-phase input power.

Two contactors (drive output and bypass); there is no drive input contactor or Test position.

In bypass the motor runs across the line at full speed, protected by a Class 20 overload relay set to the motor full-load amps.

EMB2 adds automatic transfer to bypass on a drive fault, run permissive, and basic fire mode in bypass.

Key Features

  • Bypass: 2-contactor, EMB2 electromechanical
  • Drive output current: 13 A at 380-440 VAC, 11 A at 441-480 VAC (continuous)
  • Fuses: drive fuses
  • RFI filter: standard

Product Specifications

ManufacturerDanfoss
Model178U9249
ProductVLT HVAC Drive FC 102 panel assembly (traditional bypass)
Panel model codeS1027H5T4E3R2CCD2XXSXXZ2XGXXXXXXXXXXXXXX
Drive type codeFC-102P5K5T4E20H2XGXXXXSXXXXAXBXCXXXXDX
Motor rating7.5 HP
Drive output current, continuous (380-440 VAC)13 A
Drive output current, continuous (441-480 VAC)11 A
Drive output current, intermittent (380-440 VAC)14.3 A
Drive output current, intermittent (441-480 VAC)12.1 A
Supply voltage3-phase 460 VAC
EnclosureNEMA 3R
Bypass2-contactor bypass
Bypass controlEMB2 electromechanical bypass (Drive/Off/Bypass selector, bypass pilot light)
Bypass featuresSafety interlock, common start/stop, automatic bypass, run permissive in bypass, basic fire mode
Bypass overloadClass 20 overload relay, set to motor FLA
DisconnectMain circuit breaker
FusingDrive fuses
Control power24 VDC switch-mode power supply
Line reactor / filterNone (DC link reactor built into the drive)
RFI filterStandard
Brake chopperNone
KeypadGraphical
Conformal coatingNone
Communication cardsNone (BACnet MS/TP, Modbus RTU, Metasys N2, and Apogee FLN built into the drive)
I/O cardsNone
MotorsSingle motor
Max ambient temperature40 deg C / 104 deg F
Humidity95% non-condensing
Fuses F16A, B, CBussmann JJS-25
Fuses F13A, B600 VAC, 0.8 A, Class CC
Fuses F12250 VAC, 3 A, supplemental
Terminals L1, L2, L3/ GND62 (7.0)/ 45 (5.1) in-lb (N-m); 60 deg C Copper conductors
Terminals T1, T2, T3/ GND17 (1.9)/ 45 (5.1) in-lb (N-m); 60 deg C Copper conductors
Terminals TB17 (0.8) in-lb (N-m); Copper conductors
Seismic certificationOSHPD pre-approval OSP-0603; anchorage: rigid/flexible wall mount; SDS 2.6, z/h 1.0, ip 1.5
Electrical drawing007N5206
Mechanical drawing185B7937
Net weight108.9 lb
Shipping weight148.9 lb