177U4616

SKU: 177U4616
$3,853.70
Request a Freight Quote

Ships by truck freight. Our sales team replies with delivered pricing, usually within one business day.

Details

Details

FC 102 VFD Bypass Panel, 7.5 HP, 3-Phase 600 VAC, NEMA 1, 2-Contactor Bypass, Fused Main Disconnect

One enclosure holds the drive, EMB2 electromechanical bypass, main disconnect switch, and main and drive fuses.

Needs 3-phase input power.

Two contactors (drive output and bypass); there is no drive input contactor or Test position.

In bypass the motor runs across the line at full speed, protected by a Class 20 overload relay set to the motor full-load amps.

EMB2 adds automatic transfer to bypass on a drive fault, run permissive, and basic fire mode in bypass.

Key Features

  • Bypass: 2-contactor, EMB2 electromechanical
  • Drive output current: 9.5 A at 525-550 VAC, 9.0 A at 525-600 VAC (continuous)
  • Fuses: main and drive fuses
  • RFI filter: none

Product Specifications

ManufacturerDanfoss
Model177U4616
ProductVLT HVAC Drive FC 102 panel assembly (traditional bypass)
Panel model codeS1027H5T6E012CMM2XXSXXZXXGXXXXXXXXXXXXXX
Drive type codeFC-102P5K5T6E20HXXGXXXXSXXXXAXBXCXXXXDX
Motor rating7.5 HP
Drive output current, continuous (525-550 VAC)9.5 A
Drive output current, continuous (525-600 VAC)9.0 A
Drive output current, intermittent (525-550 VAC)10.5 A
Drive output current, intermittent (525-600 VAC)9.9 A
Supply voltage3-phase 600 VAC
EnclosureNEMA 1
Bypass2-contactor bypass
Bypass controlEMB2 electromechanical bypass (Drive/Off/Bypass selector, bypass pilot light)
Bypass featuresSafety interlock, common start/stop, automatic bypass, run permissive in bypass, basic fire mode
Bypass overloadClass 20 overload relay, set to motor FLA
DisconnectMain disconnect switch
FusingMain and drive fuses
Control power24 VDC switch-mode power supply
Line reactor / filterNone (DC link reactor built into the drive)
RFI filterNone
Brake chopperNone
KeypadGraphical
Conformal coatingNone
Communication cardsNone (BACnet MS/TP, Modbus RTU, Metasys N2, and Apogee FLN built into the drive)
I/O cardsNone
MotorsSingle motor
Drive frame sizeA3
Max ambient temperature45 deg C / 113 deg F
Humidity95% non-condensing
Fuses F15A, B, C600 VAC, 15 A, Class J
Fuses F16A, B, CBussmann LP-CC-25
Fuses F900,F901,F902Bussmann FWH-020A6F 20A
Terminals L1, L2, L3/ GND55 (6.21) / 25 (2.8) in-lb (N-m); 75 deg C Copper conductors
Terminals TB17 (0.8) in-lb (N-m); Copper conductors
Seismic certificationOSHPD pre-approval OSP-0087; anchorage: rigid wall mount; SDS 1.58, z/h 1.0, ip 1.5
Electrical drawing007N0122
Mechanical drawing176U8485
Net weight47.4 lb
Shipping weight87.4 lb