174L3262

SKU: 174L3262
$11,092.49
Request a Freight Quote

Ships by truck freight. Our sales team replies with delivered pricing, usually within one business day.

Details

Details

FC 102 VFD Bypass Panel, 30 HP, 3-Phase 208 VAC, NEMA 12, 3-Contactor Bypass, Fused Main Disconnect

One enclosure holds the drive, EMB2 electromechanical bypass, main disconnect switch, and main and drive fuses.

Needs 3-phase input power.

A drive input contactor isolates the drive from the line, and a Test position runs the motor in bypass while the drive stays powered.

In bypass the motor runs across the line at full speed, protected by a Class 20 overload relay set to the motor full-load amps.

EMB2 adds automatic transfer to bypass on a drive fault, run permissive, and basic fire mode in bypass.

Key Features

  • Bypass: 3-contactor, EMB2 electromechanical
  • Drive output current: 88 A at 200-240 VAC (continuous)
  • Fuses: main and drive fuses
  • RFI filter: standard

Product Specifications

ManufacturerDanfoss
Model174L3262
ProductVLT HVAC Drive FC 102 panel assembly (traditional bypass)
Panel model codeS102030T1E123CMM2XXSXXZ2XGXXXXXXXXXXXXXX
Drive type codeFC-102P22KT2E55H2XGX7XXSXXXXAXBXCXXXXDX
Motor rating30 HP
Drive output current, continuous (200-240 VAC)88 A
Drive output current, intermittent (200-240 VAC)96.8 A
Supply voltage3-phase 208 VAC
EnclosureNEMA 12
Bypass3-contactor bypass
Bypass controlEMB2 electromechanical bypass (Drive/Off/Bypass/Test selector, bypass pilot light)
Bypass featuresSafety interlock, common start/stop, automatic bypass, run permissive in bypass, basic fire mode
Bypass overloadClass 20 overload relay, set to motor FLA
DisconnectMain disconnect switch
FusingMain and drive fuses
Control power24 VDC switch-mode power supply
Line reactor / filterNone (DC link reactor built into the drive)
RFI filterStandard
Brake chopperNone
KeypadGraphical
Conformal coatingNone
Communication cardsNone (BACnet MS/TP, Modbus RTU, Metasys N2, and Apogee FLN built into the drive)
I/O cardsNone
MotorsSingle motor
Drive frame sizeC1
Max ambient temperature40 deg C / 104 deg F
Humidity95% non-condensing
Fuses F15A, B, C600 VAC, 150 A, Class J
Fuses F16A, B, CBussmann JJN-125
Fuses F900,F901,F902Bussmann FWH-020A10F 20A
Terminals L1, L2, L3/ GND70 (7.9)/ 45 (5.1) in-lb (N-m); 75 deg C Copper conductors
Terminals T1, T2, T3/ GND40 (4.5) / 45 (5.1) in-lb (N-m); 75 deg C Copper conductors
Terminals TB17 (0.8) in-lb (N-m); Copper conductors
Seismic certificationOSHPD pre-approval OSP-0087; anchorage: rigid wall mount; SDS 1.58, z/h 1.0, ip 1.5
Electrical drawing007N1278
Mechanical drawing176U8463
Net weight161.8 lb