174L0588

SKU: 174L0588
$3,159.68
Request a Freight Quote

Ships by truck freight. Our sales team replies with delivered pricing, usually within one business day.

Details

Details

FC 102 VFD Bypass Panel, 2 HP, 3-Phase 208 VAC, NEMA 1, 2-Contactor Bypass, Main Circuit Breaker

One enclosure holds the drive, EMB2 electromechanical bypass, main breaker, and drive fuses.

Needs 3-phase input power.

Two contactors (drive output and bypass); there is no drive input contactor or Test position.

In bypass the motor runs across the line at full speed, protected by a Class 20 overload relay set to the motor full-load amps.

EMB2 adds automatic transfer to bypass on a drive fault, run permissive, and basic fire mode in bypass.

Key Features

  • Bypass: 2-contactor, EMB2 electromechanical
  • Drive output current: 7.5 A at 200-240 VAC (continuous)
  • Fuses: drive fuses
  • RFI filter: standard

Product Specifications

ManufacturerDanfoss
Model174L0588
ProductVLT HVAC Drive FC 102 panel assembly (traditional bypass)
Panel model codeS102002T1E012CCD2XXSXXZ2XGXXXXXXXXXXXXXX
Drive type codeFC-102P1K5T2E20H2XGXXXXSXXXXAXBXCXXXXDX
Motor rating2 HP
Drive output current, continuous (200-240 VAC)7.5 A
Drive output current, intermittent (200-240 VAC)8.3 A
Supply voltage3-phase 208 VAC
EnclosureNEMA 1
Bypass2-contactor bypass
Bypass controlEMB2 electromechanical bypass (Drive/Off/Bypass selector, bypass pilot light)
Bypass featuresSafety interlock, common start/stop, automatic bypass, run permissive in bypass, basic fire mode
Bypass overloadClass 20 overload relay, set to motor FLA
DisconnectMain circuit breaker
FusingDrive fuses
Control power24 VDC switch-mode power supply
Line reactor / filterNone (DC link reactor built into the drive)
RFI filterStandard
Brake chopperNone
KeypadGraphical
Conformal coatingNone
Communication cardsNone (BACnet MS/TP, Modbus RTU, Metasys N2, and Apogee FLN built into the drive)
I/O cardsNone
MotorsSingle motor
Drive frame sizeA2
Max ambient temperature45 deg C / 113 deg F
Humidity95% non-condensing
Fuses F16A, B, CBussmann LP-CC-15
Fuses F900,F901,F902Bussmann FWH-020A6F 20A
Terminals L1, L2, L3/ GND62 (7.0)/ 25 (2.8) in-lb (N-m); 75 deg C Copper conductors
Terminals T1, T2, T3/ GND20 (2.3)/ 25 (2.8) in-lb (N-m); 75 deg C Copper conductors
Terminals TB17 (0.8) in-lb (N-m); Copper conductors
Seismic certificationOSHPD pre-approval OSP-0087; anchorage: rigid wall mount; SDS 1.58, z/h 1.0, ip 1.5
Electrical drawing007N0022
Mechanical drawing176U8485
Net weight38 lb
Shipping weight78 lb