IOD-8DOR-S-S

SKU: IOD8DORSS

This item is IN STOCK

Current Stock: 1

Details

Details

Controlco Product Information Tabs
Product DetailsSpecificationsDownloads

Product Information


Optimizer 8 Relay Digital Outputs Panel Bus Module with display and Hand-Off-Auto function, screw terminal block with touchflake connection for use with Optimizer Advanced plant controller


The I/O Modules connect directly to the controller using the touch flake connections. The touch flakes are the hardware connections that provide the power and communication bus to the I/O Modules. The Wiring Adapter also provides power and communications to the I/O Modules, which is typically used when the power and the communication bus needs to be extended to an additional row of I/O Modules or to a remote panel. The Wiring Adapter can be powered with the same or a separate power supply than the controller. The I/O Modules are programmable using the Optimizer Workbench, the Comfort & Energy Workbench or the ComfortPoint Open Studio Tool. Software updates, configuration, and commissioning are all done automatically by the controller for all I/O Modules.

Specifications


Integrated Actuator Specifications

Dimensions


ParameterSpecification
I/O Module Dimensions (105 mm)4.31 x 2.44 x 4.7 inches (109.5 x 62 x 119.4 mm)
I/O Module Dimensions (70 mm)2.93 x 2.44 x 4.7 inches (74.5 x 62 x 119.4 mm)
Wiring Adapter Dimensions0.87 x 1.92 x 4.7 inches (22.1 x 48.7 x 119.4 mm)
I/O Hot Swap Base (105 mm)5.53 x 1.9 x 4.7 inches (140.5 mm x 49 mm x 119.4 mm)
I/O Hot Swap Base (70 mm)4.15 x 1.9 x 4.7 inches (105.5 mm x 49 mm x 119.4 mm)


Electrical Specifications


ParameterSpecification
Operating Voltage (AC)19 to 29 VAC (50/60 Hz)
Operating Voltage (DC)19 to 29 VDC
Overvoltage Protection Protected against overvoltage of max. 29 VAC or 40 VDC.
Terminals protected against short-circuiting.


Power Consumption


I/O Module TypesInput/Output Status Maximum current consumption from all channels including the I/O Module
CURRENT @24VAC (A)CURRENT @24VDC (A)POWER @24VAC (VA)POWER @24VDC (W)
IO-8UIO
IOD-8UIO
All 8 Channels Configured as AO/DO (max 10 V and 20 mA)0.720.3417.38.2
All 8 Channels Configured as AI (Thermistor/Voltage sensor/Current sensor)0.60.2614.46.2
All 8 Channels Configured as DI - Inputs are ON0.60.2614.46.2
IO-8AO
IOD-8AO
All 8 Channels Configured as AO/DO(max 10 V and 20 mA)0.590.2614.26.2
IO-4UIO
IOD-4UIO
All 4 Channels Configured as AO/DO (max 10 V and 20 mA)0.580.26146.2
All 4 Channels Configured as AI (Thermistor/Voltage sensor/Current sensor)0.520.2212.55.3
All 4 Channels Configured as DI - Inputs are ON0.520.2212.55.3
IO-8DIAll 8DI Channels - Inputs are ON0.2150.0855.22
IO-4DOR
IOD-4DOR
IO-4DORE
IOD-4DORE
All 4 Relay Channels - Outputs are ON0.2350.085.62


Operational Environment


ParameterSpecification
Ambient Operating Temperature -40 to 150 °F (-40 to 65.5 °C) For non-HOA models, Wiring Adapter, Hot Swap Base, and Auxiliary Terminal Block.
-4 to 150 °F (-20 to 65.5 °C) For HOA models.
Ambient Operating Humidity5 to 95 % relative humidity (non-condensing)
Shipping and Storage Temperature-40 to 158 °F (-40 to 70 °C) for I/O Modules, Wiring Adapter, Hot Swap Base, and Auxiliary Terminal Block.
Vibration Under Operation0.024” double amplitude (2 to 30 Hz), 0.6 g (30 to 300 Hz)
Dust & Vibration StandardsAccording to EN60730-1
RFI, EMI ComplianceCommercial, light, industrial, and residential environments
ElevationUp to 13123 ft. (4000 meters) from sea level.
MTBF11.5 years (Mean Time Between Failure)