H308
Details
Details
Veris H308 0.75-50A Current Switch
Detects belt loss, coupling shear, and other drops in load current. Works on VFD outputs (12-115 Hz) for on/off status only.
Key Features
- Trip point: adjustable, 0.75A min.
- Status output: NO 1A @ 30 VAC/DC
- Core: split-core, fits conductors up to 0.3 in.
Product Specifications
| Current Measurement Range | 0.75 to 50 A |
|---|---|
| Current Sensor type | Current Switch, AC |
| Electrical Wiring Size | 22 to 16 AWG (0.3 to 1.3 mm2) |
| Measurement Type | AC Current |
| Monitored Frequency Range | 50/60 Hz; on/off status only on VFD outputs at 12 to 115 Hz |
| Monitored Wire Size | 0.3" (8 mm) |
| Mounting | Split-Core |
| Operating Humidity | 10 to 90% RH, non-condensing |
| Operating Temperature | 5 to 140 deg F (-15 to 60 deg C) |
| Output Specifications | NO 1 A @ 30 VAC/DC |
| Outputs | Switch output |
| Product Certification | UL | CE |
| Setpoint | Adjustable; minimum trip 0.75 A or less |
| Warranty | 5 years |
| Detection | Belt loss, coupling shear, and mechanical failure (adjustable trip point) |
| Sensor Power | Induced from monitored conductor |
| Insulation Class | 600 VAC RMS (UL), 300 VAC RMS (CE) |
| Hysteresis | 10% (typical) |
| Terminal Block Torque | 3.5 to 7 in-lb (0.8 N-m) |
| Agency Approvals | UL 508 open device listing (functional insulation only); CE: EN61010-1, CAT III, Pollution Degree 2 |